<8. Setting Parameters>

8-24

IM 01C27B01-01EN

8.4 Self-Diagnostics

8.4.1 Identify Problems by Using the

Device Configuration Tool

First, check Diagnostic Status of the self-diagnostic

result.

Table 8.3

Diagnostic Status

Bits

Contents

Example

NAMUR NE107

Categorization

Bit31 (MSB)

F: Failure status

---

Bit30

C: Function check status

---

Bit29

O: Out of specification status

---

Bit28

M: Maintenance required status

---

Bit27

Faults in electronics

F

Bit26

Faults in sensor or actuator element

F

Bit25

Installation, calibration problem

C

Bit24

Out of service

C

Bit23

Outside sensor limits

O

Bit22

Environmental conditions out of device specification

O

Bit21

Fault prediction: Maintenance required

M

Bit20

Power is critical low: maintenance need short-term

M

Bit19

Power is low: maintenance need mid-term

M

Bit18

Software update incomplete

C

Bit17

Simulation is active

C

Bit16**

Faults due to process influence

F

Bit15**

Faults due to non-compliance with specified operating conditions

F

Bit14**

Other faults

F

Bit13-Bit08

reserved by WCI

---

Bit07-Bit01

vendor specific area

---

Bit00

Detail information available

1: available

0: no available

---

Checking the Diagnostic Status category allows

taking the proper action. The Diagnostic Status

contents are common for all ISA devices, and the

setting for the Diagnostic Status category can be

changed. For further details, refer to Diagnostic

Status Detail.

In Diagnostic Status Contents that can be

diagnosed by the EJX, the alert category set in Out

of Service can be changed to Check function. To do

so, follow one of the procedures below.

a) UAPMO block: UAP Option, select enable.

b) UAPMO block: Diagnostic Configuration,

change Out of Service from Failure to Check

function.

c) UAPMO block: UAP Option, select disable.

UAPMO block: Diagnostic Status

Any of the four categories (Check function,

Maintenance required, Failure, and Off

specification) according to NAMUR NE107* is

supplied to Diagnostic Status of each diagnostic

result.

The contents of diagnostic status are defined either

valid or invalid at Diagnostic Switch parameter.

Follow the example below to change “Out of

Service” to invalid.

a) UAPMO block: UAP Option, select enable.

b) UAPMO block: Diagnostic Switch, turn ON

Turn off “Out of Service”. Out of Service.

c) UAPMO block: UAP Option, select disable.

Note: Be careful when changing the alert category and turning

detection on and off as described above. Be sure to set

UAP OPTION to disable again to prevent setting errors.

*: NAMUR NE107 “Self-Monitoring and Diagnosis of

Field Devices”

In Diagnostic Configuration setting, select one from the

followings; F: Failure status, C: Function check status,

O: Out of specification status, or M: Maintenance

required status.

**: Applicable for Detachable antenna type (Amplifier

housing code: 8 or 9).