Operation, 1 preparation for starting operation, Operation -1 – Yokogawa EJX430B User Manual

Page 33: Preparation for starting operation -1

Advertising
background image

<7. Operation>

7-1

IM 01C27B01-01EN

7. Operation

7.1 Preparation for Starting

Operation

This section describes the operation procedure

for the EJX110B as shown in figure 7.1 (vertical

impulse piping type, high-pressure connection:

right side) when measuring the liquid flow rate, and

EJX430B as shown in figure 7.2 when measuring

pressure.

NOTE

It is required to set security and network

information to enable the transmitter to be

connected to the Field Wireless Network. For

more details, refer to section 7.4 “Connecting to

the Field Wireless Network”.

NOTE

Check that the process pressure tap valves,

drain valves, and 3-valve manifold stop valves

on both the low pressure and high pressure

sides are closed, and that the 3-valve manifold

equalizing valve is opened.

(a) Follow the procedures below to introduce

process pressure into the impulse piping and

transmitter.

■ Differential Pressure Transmitters

1) Open the low pressure and high pressure tap

valves to fill the impulse piping with process

liquid.

2) Slowly open the high pressure stop valve to fill

the transmitter pressure-detector section with

process liquid.

3) Close the high pressure stop valve.

4) Gradually open the low pressure stop valve and

completely fill the transmitter pressure-detector

section with process liquid.

5) Close the low pressure stop valve.

6) Gradually open the high pressure stop valve. At

this time, equal pressure is applied to the low

and high pressure sides of the transmitter.

7) Check that there are no liquid leaks in the

impulse piping, 3-valve manifold, transmitter, or

other components.

■ Gauge/Absolute Pressure Transmitters

1) Open the tap valve (main valve) to fill the

impulse piping with process fluid.

2) Gradually open the stop valve to introduce

process fluid into the transmitter pressure-

detector section.

3) Confirm that there is no pressure leak in

the impulse piping, transmitter, or other

components.

(b) Venting Gas from the Transmitter Pressure-

detector Section

Since the piping in the example of figure 7.1

is constructed to be self-venting, no venting

operation is required. If it is not possible to

make the piping self-venting, refer to subsection

7.5 for instructions. Leave the equalizing valve

open even after venting gas.

(c) Insert batteries into the battery case, and install

to the transmitter. To insert batteries into the

battery case, be careful to polarity of batteries

and battery case. For details of Installation of

battery, refer to section 9.4.6 and 9.4.7.

Battery case is installed in the transmitter when

shipped from the factory, however, batteries are

sold separately and not included.

(d) Using the device configuration tool, confirm

that the transmitter is operating properly. Check

parameter values or change the setpoints as

necessary.

Integral Indicator’s indication can be used

to confirm that the transmitter is operating

properly. For details on how to confirm, refer to

subsection 8.4 “Self-Diagnostics.”

ISA100 devices display self-diagnostic

information in an easy-to-understand manner

using four categories (Check function,

Maintenance required, Failure, and Off-

specification) according to NAMUR NE107*.

* NAMUR NE107 “Self-Monitoring and Diagnosis of Field

Devices”

Advertising
This manual is related to the following products: