<4. Installation>

4-1

IM 01C27B01-01EN

4. Installation

4.1 Precautions

Before installing the transmitter, read the cautionary

notes in section 2.4, “Selecting the Installation

Location.” For additional information on the

ambient conditions allowed at the installation

location, refer to subsection 11.1 “Standard

Specifications.”

NOTE

To connect this transmitter to the Field Wireless

Network, information for connecting to the field

wireless devices needs to be set beforehand.

Refer to 7.4 “Connecting to the Field Wireless

Network.”

IMPORTANT

• When welding piping during construction,

take care not to allow welding currents to

flow through the transmitter.

• Do not step on this instrument after

installation.

• For the EJX430B, the atmospheric opening

is located on the low pressure side cover

flange. Take care do not enter rain into the

opening. The opening must not face upward.

See section 11.4, “Dimensions,” for the

location of the opening.

4.2 Mounting

■ The transmitter is shipped with the process

connection, according to the ordering

specifications. To change the orientation of the

process connections, refer to section 4.3.

■ With differential pressure transmitters,

the distance between the impulse piping

connection ports is usually 54 mm (figure 4.1).

By changing the orientation of the process

connector, the dimension can be changed to

51 mm or 57 mm.

■ The transmitter can be mounted on a nominal

50 mm (2-inch) pipe using the mounting bracket

supplied, as shown in figure 4.2 and 4.3.

The transmitter can be mounted on either a

horizontal or a vertical pipe.

■ When mounting the bracket on the transmitter,

tighten the (four) bolts that hold the transmitter

with a torque of approximately 39 N·m {4kgf·m}.

57 mm

54 mm

51 mm

F0401.ai

Figure 4.1

Process Connector Impulse Piping

Connection Distances for Differential

Pressure Transmitters

CAUTION

When the suffix code of the mounting bracket

is “B,” make sure to put the spacer between the

bracket and transmitter as shown in Figure 4.2.