2 zero point adjustment, Zero point adjustment -2, Important – Yokogawa EJX430B User Manual

Page 34

Advertising
background image

<7. Operation>

7-2

IM 01C27B01-01EN

Orifice

Tap valve

(high pressure)

Tap valve

(low pressure)

3-valve manifold

Drain valve

(high pressure)

Stop valve

(low pressure)

Stop valve

(high pressure)

Equalizing valve

F0701.ai

Figure 7.1

Liquid Flow Measurement

F0702.ai

Tap valve

Drain valve

Vent plug (Fill plug)

Stop valve

Figure 7.2

Liquid Pressure Measurement

■ Confirm that transmitter is operating

properly by integral indicator.

If the transmitter is faulty, an error code is displayed.

F0703.ai

Self-diagnostic error on integral indicator

(Faulity transmitter)

Figure 7.3

Integral Indicator with Error Code

NOTE

If any of the above errors are indicated on the

display of the integral indicator or the device

configuration tool, refer to subsection 9.5.3 for

the corrective action.

■ Verify and Change Transmitter Parameter

Setting and Values

The parameters related to the following items are

minimum required to be set for operation, and set at

factory as specified in order. Confirm or change the

parameters if needed.

• Measurement range(measurement lower/upper

limit, unit)

• Output (Non linearization mode / Sq root mode)

7.2 Zero Point Adjustment

After completing preparations for operating the

transmitter, adjust the zero point. There are two

zero point adjusting ways.

IMPORTANT

Do not turn off the power to the transmitter

immediately after performing a zero point

adjustment. Powering off within 30 seconds of

performing this procedure will return the zero

point to its previous setting.