<7. Operation>

7-5

IM 01C27B01-01EN

(a) Deep sleep

F0707.ai

(b) Ready and pause

F0708.ai

(c) Confirm connecting status

F0709.ai

(d) Join

F0710.ai

NOTE

If the transmitter searches the Field Wireless

Network for long time at low ambient

temperature condition, sometimes error “AL.70

LOWBAT” is displayed on the Integral Indicator.

Even though using new batteries, it can occur. It

occurs because of battery characteristics. After

joining to the Field Wireless Network, this error

will be cleared within one hour if battery has no

failure.

7.5 Shutting Down the

Transmitter

Shut down the transmitter as follows.

1) Remove the battery pack or set the

transmitter to deep sleep mode by the Device

Configuration Tool.

2) Close the low pressure stop valve.

3) Open the equalizing valve.

4) Close the high pressure stop valve.

5) Close the high pressure and low pressure tap

valves.

NOTE

• Whenever shutting down the transmitter for

a long period, remove any process fluid that

is in the impulse piping and in the transmitter

pressure-detector section.

• The equalizing valve must be left OPEN.

• Refer to subsection 9.4.6 “Replacing the

Battery Pack” for the battery pack removing.

• When storing the instrument with a battery

pack inserted, it is recommended to put the

instrument into deep sleep mode to conserve

battery power. For details on how to switch to

deep sleep mode, refer to subsection 8.3.16

“Switching to the Deep Sleep Mode.”