D3-50, Important – Yokogawa YFGW410 User Manual
Page 111

<D3. Constructing a Field Wireless System>
D3-50
IM 01W02D01-01EN
The folder and file names for CF files have the following format. Therefore, it is necessary to
select a file that matches the revision of the model to be registered.
<Vendor ID>\<Model ID>¥<Device Revision><DD Revision><CF Revision>.cff
IDs of Yokogawa Field Wireless Devices
Item
Description
Vender ID
00594543
Model ID
EJX
000C
YTA
0005
YTMX
1802
When the [OK] button is clicked, the window shown in Figure D3-52 appears. The name of added
and registered CF files appear in the [CF File] drop-down box. In the same manner, register the
CF files of all models to register sampling data.
IMPORTANT
If a CF file unsuitable for the field wireless device is specified, it joins the field wireless network
but published data may not be sent in some cases. If this occurs, check the <Vendor ID><Model
ID><Device Revision><DD Revision><CF Revision> format. If data does not match, configure
the correct information.
IMPORTANT
Always register the CF file, even if periodic publishing is not performed.