<C1. Installation Environment>

C1-1

IM 01W02D01-01EN

Part C Installation

This part describes the installation of the YFGW410.
Follow the steps below to use of the product.
1. YFGW410 installation
2. Power, ground, and signal cable connection

C1. Installation Environment

The system must be installed in an appropriate environment to ensure stable system operation.
The following defines the detailed specifications of the YFGW410 installation environment.

Table C1-1 Installation environment specifications

Item

Specifications

Applicable

standards

Ambient

temperature

Operating

-40 to 65°C (at altitude below 2000 meters)
-40 to 55°C (at altitude between 2000 and 3000

meters)

Transport or stor-

age

-40 to 85°C

Ambient

humidity

Operating

5 to 95% relative (without condensing)

Transport or stor-

age

5 to 95% relative (without condensing)

Temperature

gradient

Operating

Within +/-10°C per hour

JEIDA 29 Class B

Transport or stor-

age

Within +/-20°C per hour

Protection class

IP20

IEC529

Vibration resistance

0.15 mm P-P (5 to 58 Hz)

IEC68-2-6

1 G (58 to 150 Hz)

Impact resistance

15 G, 11 ms (no conductive, and 3-direction half sine

waves)

IEC68-2-27

Altitude

Up to 3000 meters (due to restricted ambient tem-

perature)

Noise level

Electric field

3 V/m or less (80 MHz to 1 GHz)

Electrostatic

discharge

4 kV or less (contact discharge), 8 kV or less (aerial

discharge)

Grounding

Class D grounding

Cooling

Natural cooling

Mounting

Mounted on DIN rails.

Power

supply

Voltage range

10.8 to 26.4 VDC

Rated voltage

24 VDC

Allowable ripple

Less than 1% p-p

Power consumption

10 W

CAUTION

When ambient temperature is beyond 50

°C

, a temperature of the surface is very high. Please be

careful not to touch with bare hands.