<C4. Wiring>

C4-8

IM 01W02D01-01EN

l

Applicable cables

Insulated cables for industrial equipment such as;

• 600V polyvinyl chloride insulated wires (IV); JIS C3307
• Polyvinyl chloride insulated wires for electrical apparatus (KIV); JIS C3316
• 600V grade heat-resistant polyvinyl chloride insulated wires (HIV); JIS C3317
• Heatproof vinyl insulated wires VW-1 (UL1015/UL1007)

l

Wire Size

Core: AWG14 to 13 (2 mm

2

to 2.6 mm

2

)

l

Termination

Use a ring tongue terminal for M4 terminals: with an insulation sleeve

C4.4 Communication Cable Connection

n

Field wireless backbone device

Connect the 100BASE-TX compliance cable, terminated with an RJ-45 connector, to the field

wireless backbone device interface on the front panel of the YFGW410.

FC0408.ai

Figure C4-6 Connection to field wireless backbone

n

Field network

Connect the 100BASE-TX compliance cable, terminated with an RJ-45 connector, to the field

network interface on the front panel of the YFGW410.
Generally, connect the host system which transmits data using the ISA100.11a protocol to the F1

port of YFGW410. Connect the host system which transmits data using the Modbus/TCP proto-

col to the F2 or F3 port.

n

RS-485

YFGW410 supports to communicate with the host system, which supports Modbus/RTU commu-

nication, via the RS-485 connector on top of the main body. 4-wire and 2-wire types are provided

for connection with the host system. Selecting connection type is set by RS-485 configuration

switches. YFGW410 supports only 1 to 1 connection.
RS-485 connector is a 6-pin connector with a spring terminal (Phoenix Contact FKC 2.5/6-STF).

For details of wiring, see C4.2 Power Supply Cable Connection. Regarding RS-485 communi-