A1-2, Important – Yokogawa YFGW410 User Manual

Page 15

Advertising
background image

<A1. Minimum System Configuration>

A1-2

IM 01W02D01-01EN

Up to 20 field wireless subnets can be connected to the YFGW410.
Any of the three types of field wireless backbone can be selected for between YFGW410 and

YFGW510.

• The metal network composed of the YFGW510 (100BASE-TX model), shown in Figure

A1-1

• The optical fiber network shown in Figure A1-2, composed of the YFGW610 connected to

the YFGW410, uses the YFGW510 (100BASE-FX model) for signal transmission via optical

fiber cables.

• The wireless LAN network shown in Figure A1-3, composed of other manufactures’ wireless

LAN access point (connected to the YFGW410) for wireless LAN communication with the

YFGW510 (wireless LAN client model).

The Field Wireless Management Console, which is the program built in to the YFGW410, is used

for configuration and management of a field wireless network. This program can be started and

operated by the PC connected via the field network interface or via the maintenance interface of

the YFGW410.
Certain parameters need to be set on the following devices to configure and start the wireless

network. For the relevant procedure, see the Provisioning and Configuration section.

• YFGW410

The device parameters, wireless network configuration, commu-

nication with host system, and others

• YFGW510

The device parameters
Wireless LAN parameters if the wireless LAN client model is

selected

• Field wireless devices

Provisioning and sensor parameters, and others

Once the field wireless network has started, the field wireless device parameters can be set and

those devices can be managed from the Plant Resource Manager (PRM) connected to the host

network. If the security policy for the host system is acceptable, the FieldMate can be used for

parameter setup and maintenance. The FieldMate is connected to the YFGW410 via the mainte-

nance interface.

IMPORTANT

When CENTUM VP is running, set and adjust the parameters of the field wireless device from

PRM.
When CENTUM VP is not running, or when a non-Yokogawa host system is connected, the pa-

rameters can be set and adjusted using FieldMate.

Advertising