C4.3 grounding, C4.3, C4-6 – Yokogawa YFGW410 User Manual

Page 44

Advertising
background image

<C4. Wiring>

C4-6

IM 01W02D01-01EN

C4.3 Grounding

Appropriate grounding is necessary for the stable operation of YFGW410. The YFGW410 has

two ground terminals: the frame ground (FG) terminal secured by the M4 screw at the side of

power supply connector (on the top side of the mainbody), and the ground terminal at the power

supply spring terminal.
Connect the ground cable from the frame ground (FG) terminal to the ground. Connect the cable

shield or others to the power supply spring terminal.The internal wiring of YFGW410 mainbody is

connected as shown in the following fi gure.

YFGW410 Housing

-

+

NC

SG

RX -

RX +

TX -

TX +

Power supply

connector

RS-485

connector

Ground

terminal

FC0406.ai

Figure C4-4 Internal connection of the ground terminal

To ensure stable grounding, insulate the panel or DIN rails with YFGW410 from the metal surface

of external cabinet, rack and others by using insulation bushings or others. Then, connect the ca-

ble from YFGW410 to the ground. Class D grounding (the third class grounding) with the ground

resistance of 100 ohms or less is necessary. To connect the ground cable to YFGW410 directly,

use the frame ground (FG) terminal on the top side of the mainbody. YFGW410 should not share

a ground wire with other devices.