F2. yfgw410, F2.1 status information, F2.1 – Yokogawa YFGW410 User Manual

Page 187: F2-1

Advertising
background image

<F2. YFGW410>

F2-1

IM 01W02D01-01EN

F2. YFGW410

This Chapter describes the details of the YFGW410 status information and the troubleshooting

procedure.

F2.1 Status Information

YFGW410 operating status information is notified with the gateway status (GW_STATUS) on the

Modbus register.
The data structure and the contents of status information are as follows.

Table F2-1 Gateway Status (GW_STATUS)

Modbus

Address

Name

Data Type

Contents

n

Data status

Unsigned16

Always 0x0080: Normal

n+1

Gateway status

Unsigned16

GW0/1 system error (0: No error, 1: Error detected)

GW1 in redundant system, GW0 in single system

n+2

Unsigned16

GW2 system error (0: No error, 1: Error detected, 0xFFFF:

Not used)

n+3

Unsigned16

GW0/1 system status (0: Ready, 1: Active, 2: Standby)

GW1 in redundant system, GW0 in single system

n+4

Unsigned16

GW2 system status (0: Ready, 1: Active, 2: Standby, 0xFFFF:

Not used)

n+5

Unsigned16

Status of field wireless device

0: No error (Join for all field wireless devices)

1: Error detected. (Leave for one or more field wireless de-

vices)

n+6 to n+8

Unsigned16

Always 0 (Reserved bits)

Whether YFGW410 is normal or abnormal is notified with status information of (n+1) and (n+2).

If the YFGW410 is normal, the device operating status is notified with status information of (n+3)

and (n+4).
Whether field wireless devices registered in YFGW410 are normally connected is notified with

status information of (n+5).
This status information is imported as data via Modbus into the host system and used on the ap-

plication that displays the status of each device.
For details on how to import information with a host system and create an application, see the

user’s manual of the relevant system.