<D3. Constructing a Field Wireless System>

D3-58

IM 01W02D01-01EN

D3.2.8 Modbus Settings

When [Modbus Settings] is selected in the menu tree of the Configurator, the tab shown in Figure

D3-59 appears.

FD0363.ai

Figure D3-59 Modbus Settings Tab

The main window is comprised of three tabs: [Modbus Settings], [Input Registers], and [Holding

Registers].

l

Modbus Settings Tab

When the [Modbus Settings] tab is selected, the tab shown in Figure D3-59 appears.
At this tab, configure the Modbus mapping type.
There are two mapping types: normal mapping and data type mapping.

• With normal mapping, the status and value of the parameters which send to a host system

can be combined and mapped.

• With data type mapping, the status and value of the parameters which send to a host sys-

tem are separated and mapped to respective areas.

For host systems with 10000 Modbus registers, status values are allocated from register

number 5000.

For host systems with 65536 Modbus registers, status values are allocated from register

number 20000.

The default setting for [Start of status registers] is 20000.

The default Modbus setting is [Normal Mapping].
To change the Modbus mapping method, select the relevant button. When the button selection is

changed, the dialog shown in Figure D3-60 appears.