<G2. Field Wireless Network>

G2-6

IM 01W02D01-01EN

l

Maximum number of devices connectable to routing device

Up to 4 routing devices and up to 15 IO devices can be connected to the low-level side of rout-

ing device. However, network resources to be used are different between routing device and IO

device, and the topology of up to 4 hops is supported. Therefore, the number of devices connect-

able to each routing device is determined based on the following formula.

Number of IO devices + Number of routing devices x 3 ≤ 30

For example, if there are 4 routing devices, up to 15 IO devices can be connected.

G2.6.2 Maximum Number of Host Systems

YFGW410 supports 240 accesses per second on sum of three field network interfaces. A number

of access from the host systems should be configured within 240 accesses per second. When a

number of accesses from the host system exceeds this, communication between YFGW410 and

the host system may be delayed or unstable. In this case, it requires restarting YFGW410.
A guide line of accessing;

For 1 to 3 Modbus/TCP clients:

Up to 50 accesses per second for each client.

For 4 to 8 Modbus/TCP clients:

Up to 30 accesses per second for each client.

For Modbus/RTU client:

Up to 10 accesses per second.

For field wireless OPC server (SSS7100):

A number of accesses is depended on amount of field wireless devices and publish mes-

sages.

For details, consult our service or sales representative.

G2.6.3 Duocast and Auto I/O Device

The Duocast-specified backbone router cannot be connected to the Auto I/O device in the same

field wireless subnet.