Installing impulse piping, 1 impulse piping installation precautions, 1 connecting impulse piping to a transmitter – Yokogawa EJX530B User Manual

Page 23: 2 routing the impulse piping, Installing impulse piping -1, Impulse piping installation precautions -1 5.1.1, Connecting impulse piping to a transmitter -1, Routing the impulse piping -1, Important

Advertising
background image

<5. Installing Impulse Piping>

5-1

IM 01C27F01-01EN

5. Installing Impulse Piping

5.1 Impulse Piping Installation

Precautions

The impulse piping that connects the process

outputs to the transmitter must convey the process

pressure accurately. If, for example, gas collects in

a liquidfilled impulse line, or the drain for a gas-filled

impulse line becomes plugged, it will not convey the

pressure accurately. Since this will cause errors in

the measurement output, select the proper piping

method for the process fluid (gas, liquid, or steam).

Pay careful attention to the following points when

routing the impulse piping and connecting the

impulse piping to a transmitter.

5.1.1 Connecting Impulse Piping to a

Transmitter

IMPORTANT

The transmitter can be installed in horizontal

impulse piping configuration, tilting the

transmitter's position up to 90°. When tilting,

observe that the pipe (for Model EJX530B

with measurement span code A, B, and C) is

positioned horizontal downwards, or any place

between them, as shown in Figure 5.1 The

zero-adjustment screw must be positioned

downwards for all the models.

F0501.ai

Zero-adjustment screw

Pipe

(backside of the instrument)

The pipe (open to atmosphere) is positioned horizontal.

If the zero-adjustment screw is positioned other than

downwards after installation, rotate the housing until it is

positioned downwards.

Figure 5.1

Horizontal Impulse Piping Connection

5.1.2 Routing the Impulse Piping

(1) Process Pressure Tap Angles
If condensate, gas, sediment or other extraneous

material in the process piping gets into the impulse

piping, pressure measurement errors may result. To

prevent such problems, the process pressure taps

must be angled as shown in figure 5.2 according to

the kind of fluid being measured.

NOTE

• If the process fluid is a gas, the taps must be

vertical or within 45° either side of vertical.

• If the process fluid is a liquid, the taps must

be horizontal or below horizontal, but not

more than 45° below horizontal.

• If the process fluid is steam or other

condensing vapor, the taps must be

horizontal or above horizontal, but not more

than 45° above horizontal.

[Gas]

Pressure

taps

Process

piping

[Steam]

[Liquid]

45°

45°

45°

45°

45°

45°

F0502.ai

Figure 5.2

Process Pressure Tap Angle

(For Horizontal Piping)

(2) Position of Process Pressure Taps and

Transmitter

If condensate (or gas) accumulates in the impulse

piping, it should be removed periodically by

opening the drain (or vent) plugs. However, this will

generate a transient disturbance in the pressure

measurement, and therefore it is necessary to

position the taps and route the impulse piping so

that any extraneous liquid or gas generated in the

leadlines returns naturally to the process piping.

• If the process fluid is a gas, then as a rule the

transmitter must be located higher than the

process pressure taps.

• If the process fluid is a liquid or steam, then as a

rule the transmitter must be located lower than

the process pressure taps.

Advertising
This manual is related to the following products: