<11. General Specifications>

11-1

IM 01C27F01-01EN

11. General Specifications

11.1 Standard Specifications

Communication protocol:

ISA100.11a protocol

Data rate:

250 kbps

Frequency:

2400 - 2483.5 MHz license free ISM band

Radio security:

AES 128 bit codified

RF Transmitter power:

Max. 11.6 dBm (fixed)

Antenna:

+2 dBi Omni directional monopole type

Span and range limits:

(For EJX510B, values are in absolute and lower

range limits are 0.)

T01E.ai

Span

Span

Range

Range

Range

Range

Span

–1 to 20

1 to 50

–1 to 100

2 to 100

0.4 to 20

145 to 7200

10 to 500

8 to 200 kPa

–0.1 to 10

–0.1 to 2

0.04 to 2

–100 to 200 kPa

–14.5 to 1450

0.2 to 10

1.16 to 29

–14.5 to 29

5.8 to 290

–14.5 to 290

29 to 1450

Span

–1 to 2

10 to 500

–1 to 500

–14.5 to 7200

–0.1 to 50

–1 to 500

2 to 100

–1 to 2

0.08 to 2

0.4 to 20

–1 to 20

–1 to 100

A

D

0.08 to 2

C

B

kgf/cm

2

(/D4)

MPa

Measurement

Span/Range

psi (/D1)

bar (/D3)

Performance specifications:

Refer to GS 01C27F01-01EN.

Update Time

Measurement

mode

Differential

pressure

Pressure

Continuous

100 ms

100 ms

Intermittent

0.5 to 3600 s

selectable

0.5 to 3600 s

selectable

For amplifier housing code 7:

The transmitter shifts to the countinuous mode

when the update time is set to 1 second.

Minimum update time is 1 second.

For amplifier housing code 8 and 9:

The transmitter shifts to the countinuous mode

when the update time is set to 0.5 second.

Power Supply Specifications

Battery:

Use the dedicated battery pack.

Rated voltage: 7.2 V

Rated capacity: 19 Ah

Output:

Wireless (ISA100.11a protocol) 2.4GHz signal

Zero Adjustment Limits:

Zero can be fully elevated or suppressed, within

the lower and upper range limits of the capsule.

External Zero Adjustment:

External zero is continuously adjustable with

0.01% incremental resolution of span. Re-range

can be done locally using the digital indicator

with range-setting switch.

Integral Indicator (LCD display):

5-digit numerical display, 6-digit unit display

and bar graph. The indicator is configurable

to display one or up to two of the following

variables periodically.;

Pressure and temperature.

Burst Pressure:

A, B and C capsule: 30MPa

D capsule: 132MPa

Self Diagnostics:

Capsule failure, amplifier failure,

configuration error, battery alarm,

wireless communication alarm,

and over-range error for process variables.

Ambient Temperature Limits:

-40 to 85ºC(-40 to 185°F)

-30 to 80ºC(-22 to 176°F) LCD visible range

Process Temperature Limits:

-40 to 120ºC(-40 to 248°F)

Ambient Humidity Limits:

0 to 100% RH