<8. Setting Parameters>

8-20

IM 01C27F01-01EN

(1) Zero Point Adjustment

a. To set 0% at current input, perform

following procedure.

This method is used only when the pressure at

bottom of measurement range is zero.

• Procedure to call up the lower limit adjustment

parameter (Calibration Lowest Point).

AI1 block : Calibration Lowest Point

Set 0 to Calibration Lowest Point parameter for

pressure (AI1 block).

• Procedure to call up the calibration adjustment

parameter (Cal Cmd).

AI1 block : Cal Cmd : CAL_LOW

Lower limit is changed by using Cal Cmd

parameter for puressure (AI1 block).

• Procedure to call up the calibration adjustment

parameter (Cal Status)

AI1 block: Cal Status

Confirm the calibration status of CAL_

SUCCESS (1) using the Cal Status parameter.

b. To match current input and output value,

follow procedure

Like the measurement that is impossible to

set process pressure to 0kPa, output value is

adjustment to actual level by other measurement

using glassgage.
Example:

Pressure Transmitter’s span is 0 to 25.00kPa,

current level is 13.50kPa, current output is

13.83kPa.

• Procedure to call up the lower limit adjustment

parameter (Calibration Lowest Point).

AI1 Block: Calibration Lowest Point

Set the actual level value of 13.50 kPa to the

Calibration Lowest Point parameter for the

pressure (AI1 block). Apply an actual input

and confirm the value specified in Calibration

Lowest Point as the output value.

• Procedure to call up the calibration adjustment

parameter (Cal Cmd).

AI1 block: Cal Cmd: CAL_LOW

The present output is changed from 13.83kPa

to 13.50 kPa in CAL_LOW of the pressure (AI1

block) Cal Cmd parameter.

• Procedure to call up the calibration status

parameter (Cal Status).

AI1 block: Cal Status

Confirm the calibration status of Cal Status (1)

using the Cal Status parameter.

c. Using External Zero adjustment Screw
External Zero-adjustment parameter (External

Zero Trim) can set permission or prohibition to

adjustment by External Zero-adjustment Screw.
Set “Trim on” to use the External Zero-adjustment

Screw. (“Trim on” at shipment)
Use a slotted screwdriver to turn the zero-

adjustment screw. Equalize the transmitter, then

turn the screw clockwise to increase the output or

counterclockwise to decrease the output. The zero

point adjustment can be made with a resolution

of 0.01% of the setting range. The degree of zero

adjustments varies with the screw turning speed;

turn the screw slowly to make a fine adjustment,

quickly to make a rough adjustment.

Zero-adjustment Screw

F0806.ai

Figure 8.2

Zero-adjustment Screw