<10. Parameter Summary>

10-7

IM 01C27F01-01EN

Object

ID

Attribute

ID

Label

Description

Default

value

Handling

5.

AI1

block

(continued)

106

H/L Swap

Allows performing reverse connection of the impulse

line.

(NORMAL, REVERSE : reverse connection)

Used when the lower pressure side and higher

pressure side of the impulse line were connected

wrongly when installing the pressure transmitter.

Normal

W

107

T Zero Cmp

Parameter to select the temperature zero shift

compensation mode

0 = OFF : Does not perform temperature zero shift

compensation.

1 = ON : Performs temperature zero shift

compensation.

Off

w

108

Temp Zero

Parameter to set the temperature gradient value for the

temperature zero shift compensation

0

w

109

Temp Select

Parameter to select the temperature (amplifier-side

/ capsule-side) used for the temperature zero shift

compensation.

0 = AMP TEMP : the value of the amplifier-side

temperature sensor is used.

1 = CAP TEMP : the value of the capsule-side

temperature sensor is used.

1

w

6.

AI2

block

1

Process Value

AI2 is a static pressure output object.

Indicates the primary analog value (or corresponding

process value) and status used to execute this

function.

Allows updating data by specifying this for the

Concentrator object.

1. Value: output value of Al object

2. Status: Specify output status of Al object.

---

W

2

Block Mode

A universal parameter to indicate the block’s operation

status. O/S, Auto, and Man can be selected.

1. Target : Specify Al object mode.

2. Actual : Indicates current mode of Al object.

3. Permitted : Indicates the mode selected by Target

of Al object.

4. Normal : Indicate normal status mode of Al object.

1.Target

= O/S

2.Actual

= O/S

3.Permitted

= O/S

4.Normal

= O/S

W

3

Concentrator OID

Indicates the Concentrator object value that

corresponds to the data update of the PV value.

3

R

4

Scale

Allows specifying the upper or lower limit for the PV

scaling, unit code, etc.

1. EU at 100% : Indicate the upper limit of the PV

value.

2. EU at 0% : Indicate the lower limit of the PV value.

3. Units Index : Indicate the setting unit used for the

PV value.

4. Decimal : Indicate the digit number below the

decimal point displayed in the LCD indicator.

1. EU at 100%

= 100

2. EU at 0%

= 0

3. Units Index

= %

4. Decimal

= 2

W

26

Tag Description

A universal parameter to store the comment that

describes the tag.

AI2: Static

Pressure

W

27

Process Value

Filter Time

Allows adjusting the time constant for filtering the PV

value. Setting unit: Second. This is enabled for the

Continuous mode.

0 second

W

28

Simulate Switch

A simulation function switch for the AI object test

(Disable, Enable)

Disable

W

29

Transducer Value

When Simulate Switch is set to Disable, this value is

used as the input value for the AI object.

---

R

30

Simulate Value

When Simulate Switch is set to Enable, this value is

used as the input value for the AI object.

The input value can be changed.

---

W