<8. Setting Parameters>

8-24

IM 01C27F01-01EN

8.4.2 Alert Report

EJX generates alert information related to

Diagnostic Status and automatically sends to a field

wireless gateway. To use this function, the following

alert setting is necessary. When “Out of Service” for

Diagnostic Status alert is required, choose “FALSE”

for [Out of Service.Alert Disable] in the UAPMO

block. Refer to the field wireless gateway User’s

Manual for the setting procedure to obtain the alert

information from the gateway.

The alert report consists of the list of parameter

names as shown Table 8.4 below.

Table 8.4

Contents of Alert Report

Parameter name

Description

DetectObjectTLPort Alert detection port UAP (0xF0B2)

fixed

DetectObject

Alert detection block UAPMO (1)

fixed

DetectTime

Time stamp

AlertDirection

1: generated, 0: clear

AlertPriority

Alert priorities set by users

AlertType

Alert types, see 8.4 Self-

Diagnostics

AlertValue

NAMUR107 category

0:Failure, 1:checkFunction,

2:OffSpec, 3:MaintenaceRequired

CAUTION

For a wireless gateway which does not support

the alert report function, the alert setting in

UAPMO block for the transmitter must be set

to “Disable.” Note that YFGW710 field wireless

integrated gateway does not have the alert

report function.