Yokogawa EJX530B User Manual

Page 85

Advertising
background image

<10. Parameter Summary>

10-10

IM 01C27F01-01EN

Table 10.2

Diagnostic Status Detail [0]

Bit

Diagnostic Status Detail

Description

Diagnostic Status

assignment bit

NAMUR

DiagnosticDetail_1
31

FC_SENSOR_FAIL

C sensor frequency error

Bit26

F

30

FR_SENSOR_FAIL

R sensor frequency error

Bit26

F

29

CAP_T_SENSOR_FAIL

Capsule temperature sensor failure

Bit26

F

28

CAP_EEPROM_FAIL

Capsule EEPROM failure

Bit26

F

27

CAP_EEP_IRREGULAR

CAP EEPROM version not correct

Bit26

F

26

AMP_T_SENSOR_FAIL

Amplifier temperature sensor failure

Bit27

F

25

AMP_EEPROM_FAIL

Amplifier EEPROM failure

Bit27

F

24

AMP_EEP_IRREGULAR

AMP EEPROM version not correct

Bit27

F

22

G_A_COMM_FAIL

G/A failure

Bit27

F

21

FC_UNOSC_FAIL

C sensor oscillation stop failure

Bit26

F

20

FC_DELTA_T_FAIL

C-side deltaT circuit failure

Bit27

F

19

FR_DELTA_T_FAIL

R-side deltaT circuit failure

Bit27

F

18

WL_AD_FAIL

Battery voltage not detected (AMP failure)

Bit27

F

17

FR_UNOSC_FAIL

R sensor oscillation stop failure

Bit26

F

15

DP_OUTSIDE_LIMIT

Pressure outside of specified range

Bit23

O

14

SP_OUTSIDE_LIMIT

Static pressure outside of specified range

Bit23

O

13

CAPT_OUTSIDE_LIMIT

Capsule temperature outside of specified range

Bit23

O

12

AMPT_OUTSIDE_LIMIT

Amplifier temperature outside of specified range

Bit23

O

7

DP_OUTSIDE_RANGE

Input pressure setting outside of range

Bit22

O

6

SP_OUTSIDE_RANGE

Static pressure setting outside of range

Bit22

O

DiagnosticDetail_2
31

AI1_OUT_OF_SERVICE

AI1 O/S mode

Bit24

C

30

AI2_OUT_OF_SERVICE

AI2 O/S mode

Bit24

C

29

AI3_OUT_OF_SERVICE

AI3 O/S mode

Bit24

C

28

AI1_SIMULATION_ACTIVE

AI1 simulation mode

Bit17

C

27

AI2_SIMULATION_ACTIVE

AI2 simulation mode

Bit17

C

26

AI3_SIMULATION_ACTIVE

AI3 simulation mode

Bit17

C

20

DP_TRIM_SPAN_OUTSIDE

Pressure span adjustment variable outside of range

Bit25

C

19

DP_TRIM_ZERO_OUTSIDE

Pressure zero adjustment variable outside of range

Bit25

C

15

SP_TRIM_SPAN_OUTSIDE

Static pressure span adjustment variable outside of

range

Bit25

C

14

SP_TRIM_ZERO_OUTSIDE

Static pressure zero adjustment variable outside of

range

Bit25

C

13

WL_LOWBAT_ALM

Low battery

Bit19

M

12

CRITICAL_LOWBAT

*1

Detect a decrease in the lowest drive voltage.

Bit20

M

10

WL_DEEPSLP_ALM

Deep sleep due to low battery

Bit20

M

8

LCD_OUTSIDE_LIMIT

LCD display outside of specified range

Bit25

C

F1001.ai

AI algoritm

MODE Target

from operator

from operator

from operator

from transducer

SIMULATE

On

Off

AI

algorithm

Linearization

scaling,

filter

Alert

report

HiHi etc

PV

Auto

O/S

Man

Publish

Value

& Status

PV

PV

Value

& Status

Value

& Status

Value

& Status

Mode and

PV.Status handling

SWITCH

SIMULATE

_VALUE

Figure 10.1 Example schema of analog input object