9.5.3 Errors and Countermeasures

Various diagnostics of the Al2 object and the static pressure is not supported in this instrument.

Table 9.3

Error Message Summary (Causes and Actions)

Integral

indicator

Factory

NAMUR

category

Bit

Diagnostic

Status

Diagnostic Status Detail

Cause

Release/

recovery

conditions

(except

restart)

Action

AL. 01

CAP. ERR

*2

F

Bit 26

Faults

in sensor or

actuator

element

FC_SENSOR_FAIL

Pressure sensor

failure

Recovers only

when AUTO

RECOVER is

ON and within

the range

Replace the

capsule.

FR_SENSOR_FAIL

FC_UNOSC_FAIL

Recovers only

when AUTO

RECOVER

is ON and

oscillation does

not stop

FR_UNOSC_FAIL

CAP_T_SENSOR_FAIL

Capsule

temperature

sensor failure

None

CAP_EEPROM_FAIL

Capsule

EEPROM

memory failure

Recovers

when returns to

normal.

CAP_EEP_IRREGULAR

None

AL. 02

AMP. ERR

*2

F

Bit 27 Faults in

electronics

AMP_T_SENSOR_FAIL

*3

Amplifier

temperature

sensor failure

None

Replace the

amplifier.

AMP_EEPROM_FAIL

Amplifier

EEPROM failure

Recovers

when returns to

normal.

AMP_EEP_IRREGULAR

None

FC_DELTA_T_FAIL

Amplifier failure

None

FR_DELTA_T_FAIL
G_A_COMM_FAIL
WL_AD_FAIL

AL. 10

PRESS

O

Bit 23 Outside sensor

limits

DP_OUTSIDE_LIMIT

Pressure

outside of

specified range

Recovers when

input pressure

returns within

the range.

Check

the input

pressure.

AL. 11

ST. PRSS

SP_OUTSIDE_LIMIT

Static pressure

outside of

specified range

Recovers when

static pressure

returns within

the range.

Check

the input

pressure.

AL. 12

CAP. TMP

CAPT_OUTSIDE_LMIT

Capsule

temperature

outside of range

(-50 to 130°C)

Recovers when

temperature

returns within

the range.

Retain heat

or insulate

so that

temperature

returns within

the specified

range.

AL. 13

AMP. TMP

AMPT_OUTSIDE_LIMIT

Amplifier

temperature

outside of range

(-50 to 95°C)

Recovers when

temperature

returns within

the range.

Retain heat

or insulate

so that

temperature

returns within

the specified

range.