Yokogawa EJX530B User Manual

Page 69

Advertising
background image

<9. Maintenance>

9-10

IM 01C27F01-01EN

Connect the device configuration tool and check self-diagnostics.

Contact Yokogawa service personnel.

F0909.ai

Are valves opened or

closed correctly?

Is impulse piping

connected correctly?

Refer to Alarm Message

Summary in Subsection 9.5.3.

Provide lagging and/or cooling, or allow

adequate ventilation.

Refer to subsection 9.2 "Calibration

Instruments Selection".

Fully open valve.

Refer to individual model user manuals

and connect piping as appropriate for

the measurement purpose.

Adjust the output.

Is transmitter

installed where there is

marked variation in

temperature?

Is output adjusted correctly?

Large output error.

Does the self-

diagnostic indicate problem

location?

Were appropriate

instruments used for

calibration?

YES

NO

YES

NO

NO

YES

NO

YES

NO

YES

NO

YES