2 troubleshooting flowcharts, Troubleshooting flowcharts -9 – Yokogawa EJX530B User Manual

Page 68

Advertising
background image

<9. Maintenance>

9-9

IM 01C27F01-01EN

9.5.2 Troubleshooting Flowcharts

Check display of the error code.

Check self-diagnostics by the device configuration tool.

Does the self-diagnostic

indicate problem location?

Contact Yokogawa service personnel.

F0907.ai

The following sorts of symptoms indicate that transmitter

may not be operating properly.

Example : • There is no output signal.

• Output signal does not change even though

process variable is known to be varying.

• Output value is inconsistent with value

inferred for process variable.

Fix pressure leaks, paying particular

attention to connections for impulse

piping,pressure-detector section, etc.

Fully open valve.

Are valves opened or

closed correctly?

Is there any pressure leak?

YES

NO

YES

NO

NO

YES

Refer to Alarm Message Summary in

Subsection 9.5.3.

Is the

Field Wireless Network

setting correct?

NO

YES

Reconnect to the Field Wireless

Network.

Connect the device configuration tool and check self-diagnostics.

Does the self-

diagnostic indicate problem

location?

Contact Yokogawa service personnel.

F0908.ai

Are valves opened or

closed correctly?

Refer to Alarm Message Summary in

Subsection 9.5.3.

YES

NO

Fix pressure leaks, paying particular

attention to connections for impulse

piping, pressure-detector section, etc.

Fully open valve.

NO

YES

YES

NO

Adjust the zero point.

NO

YES

Is there any pressure leak?

Is zero point

adjusted correctly?

Output travels beyond 0% or 100%.