<10. Parameter Summary>

10-8

IM 01C27F01-01EN

Object

ID

Attribute

ID

Label

Description

Default

value

Handling

6.

AI2

block

(continued)

51

Upper Limit

Indicates the upper limit (URL) for the pressure.

---

R

52

Lower Limit

Indicates the lower limit (LRL) for the pressure.

---

R

53

PV Range

Sets the measurement range.

1. EU at 100% : Indicates input value of the upper

limit.

2. EU at 0% : Indicates input value of the lower limit.

3. Units Index : Indicates the units of the

measurement range.

4. Decimal : Indicates the digit number below the

decimal point.

1. EU at

100% =

25000.000000

EU at 0%

= 0

Units Index

= kPa

Decimal

= 2

W

54

Linearization Type

Select either No Linearization or Square root as a

setting of the output range.

0 = No Linearization :

Provides an output value scaled according to the

PV Range and Scale range settings.

(To use Direct with FF, set the same value for PV

Range and Scale.)

0

W

55

Flow Constant

Indicates the flow coefficient, which shows the

correlation between the flow rate value and square root

value of the pressure.

1.0

W

56

Lower Cutoff

Specifies the low cut value. The unit is subject to

Scale.Units Index.

10

W

57

Cal Cmd

Specifies the calibration method.

0 = CAL_NONE : Initial state in which calibration is

not performed

1 = CAL_LOW : Applies an actual input and adjusts

the lower limit using the value specified in

Calibration Lowest Point.

2 = CAL_HIGH : Applies an actual input and adjusts

the higher limit using the value specified in

Calibration Highest Point.

5 = CAL_CLEAR : Clears the adjustment variable.

0 (reading

value is

always 0)

W

58

Cal Status

Indicates the calibration status.

0 = CAL_NONE : Start-up and default value

1 = CAL_SUCCESS : Indicates that calibration was

successful.

7 = CAL_BAD_TRIM_POINT : Indicates this status

when the adjustment variable is outside of range.

R

59

Calibration Highest

Point

Specifies the higher limit adjustment variable for

adjustment between two points.

---

W

60

Calibration Lowest

Point

Specifies the lower limit adjustment variable for the

adjustment between two points.

---

W

61

Calibration

Minimum Span

Indicates the minimum span of the adjustment

variable.

108 = Gauge pressure

109 = Absolute pressure

---

R

102

Static Process

Type

Selects the gauge pressure or the absolute pressure.

Abs

W

103

SP Select

Parameter to select the High-side pressure or the Low-

side pressure as the static pressure output.

0 = High : Displays the H-side pressure as the static

pressure

1 = Low : Displays the L-side pressure as the static

pressure

High

W