Sound data, Chillers optichill freecool – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 101

Advertising
background image

Chillers

OptiChill Freecool

Chillers

101

Technical Manual :

7197700 v1.2.0 02_2013

Sound Data


Measurement of sound
data

All sound data quoted has been measured in the third-octave band limited values, using
a Real Time Analyser calibrated sound intensity meter in accordance with
BS EN ISO9614 Part 1 : 1995. The Global sound data quoted is valid for noise
emitted in the horizontal plane in all directions.

All Sound Power Levels quoted are calculated from measured sound intensity according
to BS EN ISO9614 Part 1 : 1995.

Sound Pressure Levels are calculated from sound power using the expanded
parallelepiped method
according to BS EN ISO11203 : 1996.


Sound Directivity

The Global sound measurements quoted in the following tables do not incorporate any
directivity or denote any sound level heard at any given position surrounding the unit,
rather they represent the total sound level emanated from the unit in all directions in
the horizontal plane
from source.

Using the adjustment factors from the map below, specific directional sound power levels
can be derived from the global sound power data.


Base Correction Values -
Global dB



-9

-4

-8

-4


EXAMPLE:

OFC091X22-87ML5
Overall Sound Power
= 97 dB(A) ie:

93dB(A)

89dB(A)

93dB(A)

88dB(A)

Advertising
This manual is related to the following products: