Electrical Data Regular Quiet Continued

19

20

Notes

Units

OFC097R22-88MS4

OFC109R22-99HL5

Unit Data

Nominal Run Amps (1)

A

577

627

Maximum Start Amps

A

922

1166

Recommended Mains Fuse Size

A

710

750

Mains Supply

VAC

400 V 3 PH 50 Hz

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

4 mm² terminals

Control Circuit

VAC

24V/230VAC

24V/230VAC

Evaporator

Trace Heater Rating

W

250

250

External Trace Heating

Available (fitted by others)

W

500

500

Condenser Fan - Per Fan (AC)

Quantity

22

22

Full Load Amps

A

4.3

4.3

Locked Rotor Amps

A

15

15

Motor Rating

kW

2

2

Condenser Fan - Per Fan (EC)

Quantity

22

22

Full Load Amps

A

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

Motor Rating

kW

2.56

2.56

Condenser Fan - Per Fan (HAEC)

Quantity

22

22

Full Load Amps

A

4.5

4.5

Locked Rotor Amps

A

N/A

N/A

Motor Rating

kW

2.86

2.86

Compressor - Per Compressor

Quantity

1 + 1

1 + 1

Nominal Run Amps

A

241.3 / 241.3

266.2 / 266.2

Motor Rating

kW

139.5 / 139.5

152.7 / 152.7

Sump Heater Rating

W

300

300

Start Amps (2)

A

586 / 586

805 / 805

Type Of Start

Star - Delta

Star - Delta

OPTIONAL EXTRAS

Low Ambient Kit

Recommended Permanent Fuse Size

A

32

32

Permanent Supply

VAC

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

4 mm² terminals

Power Factor Correction

Unit Nominal Run Amps (1)

A

518

559

Maximum Start Amps

A

893

1132

Compressor Nominal Run Amps

A

211.9 / 211.9

232.0 / 232.0

Recommended Mains Fuse Size

A

710

750

Standard Head Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

612

648

Recommended Mains Fuse Size

A

750

800

Pump Full Load Amps

A

35

21.2

Motor Rating

kW

18.5

11

Larger Head Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

629

656

Recommended Mains Fuse Size

A

750

800

Pump Full Load Amps

A

52

28.5

Motor Rating

kW

30

15

Standard Head Inverter Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

612

648

Recommended Mains Fuse Size

A

750

800

Pump Full Load Amps

A

35

21.2

Motor Rating

kW

18.5

11

Larger Head Inverter Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

629

656

Recommended Mains Fuse Size

A

750

800

Pump Full Load Amps

A

52

28.5

Motor Rating

kW

30

15

(1) Based at 5.0 Evaporating, 50 Condensing, AC Standard Fans.

(2) Starting amps refers to the Star (

Ү) connection only.