Optichill freecool active cabinet exhaust chillers – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 36

Advertising
background image




OptiChill Freecool


Active Cabinet Exhaust

Chillers

36

Chillers

Technical Manual : 7197700 v1.2.0. 02_2013

Fan & Motor Assembly

AC Fan Motor

Sickle bladed fan assemblies with integral long bellmouth and fingerproof grille;
incorporate external rotor AC motor technology, capable of highly accurate discreet
speed control and discharges air vertically. The fans offer maximum airflow performance
while keeping sound levels to a minimum.

Each fan is speed controllable and operates from a 3 phase electrical supply.

Energy efficient Electronically Commutated (EC) fans are also available.


Compressor

Twin screw semi hermetic compressors comprising:

Electronic Protection Module featuring:

Motor, discharge gas and oil monitoring

Rotation direction protection

Phase failure protection

Low current Star/Delta Start

Internal pressure relief

Discharge non return valve

Oil separator

Oil sight glass

Oil heater

Slide valve stepped capacity control

Suction gas motor cooling

The compressors are mounted to the rigid galvanised heavy duty sub-frame with the use
of vibration reducing isolation.

Liquid injection is not required under normal operating conditions, leading to an increase
in cooling and efficiency

Closed transition Star/Delta compressor start is available as an optional extra; refer to

Design Features & Information

, on page 49 for further details.


Maintainable Dual
Pressure Relief Valve

A 3-way dual shut-off valve assembly incorporating 2 relief valves per circuit allows the
maintenance of individual pressure relief valves without the need for
refrigerant evacuation.


Refrigeration

Each refrigeration circuit is supplied with the following:

Full operating charge of R134a

Electronic Expansion Valves (EEV)

Discharge line ball valve

Liquid line ball valve

Large capacity filter drier with replaceable cores

Liquid line sight glass

Low pressure switch with Auto reset

High pressure switch with manual reset

Suction and liquid pressure transducers

Discharge line mufflers (X Models)

Advertising