Chillers

OptiChill Freecool

Chillers

85

Technical Manual :

7197700 v1.2.0 02_2013

Electrical Data Extra Quiet Continued

33

34

35

Notes

Units

OFC092X20-87HS6

OFC097X20-88HL5

OFC104X20-99HL6

Unit Data

Nominal Run Amps (1)

A

512

541

582

Maximum Start Amps

A

1071

1100

1121

Recommended Mains Fuse Size

A

630

670

710

Mains Supply

VAC

400 V 3 PH 50 Hz

400 V 3 PH 50 Hz

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Direct to Bus Bar

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

4 mm² terminals

4 mm² terminals

Control Circuit

VAC

24V/230VAC

24V/230VAC

24V/230VAC

Evaporator

Trace Heater Rating

W

250

250

250

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

20

20

20

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.27

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

20

20

20

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Condenser Fan - Per Fan (HAEC)

Quantity

20

20

20

Full Load Amps

A

4.5

4.5

4.5

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.86

2.86

2.86

Compressor - Per Compressor

Quantity

1 + 1

1 + 1

1 + 1

Nominal Run Amps

A

245.4 / 216.3

245.4 / 245.4

266.2 / 266.2

Motor Rating

kW

138.8 / 122.5

138.8 / 138.8

152.7 / 152.7

Sump Heater Rating

W

300

300

300

Start Amps (2)

A

805 / 650

805 / 805

805 / 805

Type Of Start

Star - Delta

Star - Delta

Star - Delta

OPTIONAL EXTRAS

Low Ambient Kit

Recommended Permanent Fuse Size

A

32

32

32

Permanent Supply

VAC

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

4 mm² terminals

4 mm² terminals

Power Factor Correction

Unit Nominal Run Amps (1)

A

447

472

514

Maximum Start Amps

A

1041

1066

1087

Compressor Nominal Run Amps

A

210.9 / 186.1

210.9 / 210.9

232.0 / 232.0

Recommended Mains Fuse Size

A

630

670

710

Standard Head Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

540

562

597

Recommended Mains Fuse Size

A

670

670

750

Pump Full Load Amps

A

28.5

21.2

14.8

Motor Rating

kW

15

11

7.5

Larger Head Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

547

569

611

Recommended Mains Fuse Size

A

670

710

750

Pump Full Load Amps

A

35

28.5

28.5

Motor Rating

kW

18.5

15

15

Standard Head Inverter Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

540

562

597

Recommended Mains Fuse Size

A

670

670

750

Pump Full Load Amps

A

28.5

21.2

14.8

Motor Rating

kW

15

11

7.5

Larger Head Inverter Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

547

569

611

Recommended Mains Fuse Size

A

670

710

750

Pump Full Load Amps

A

35

28.5

28.5

Motor Rating

kW

18.5

15

15

(1) Based at 5.0 Evaporating, 50 Condensing, AC Standard Fans.