Controls

Monitoring

The microprocessor also monitors and displays the following measured parameters:

Supply Water Temperature

Return Water Temperature

Evaporator Differential Water Pressure

Suction Pressure of each circuit

Liquid Pressure of each circuit

Suction Temperature at each circuit

Superheat for each circuit

Discharge temperature of each circuit

Alarm handling

The controller logs and allows viewing of the last 100 conditions recorded in descending
chronological order through the keypad display.

The following conditions will be detected, triggering a visual display:

Common for both circuits:

Low Supply Temperature

Emergency Stop

Water Flow

Volt Free Contact Alarm Indication

Individual for each circuit:

Individual alarms will isolate the affected circuit only.

Compressor Trip

Low Suction Pressure for each circuit

High Liquid Pressure for each circuit

Low Pressure Switch

Compressor Overload

High Compressor Discharge Temperature

Circuit 1 Isolator Status

Circuit 2 Isolator Status

Unit Remote ON/OFF

Disables/Enables the unit remotely.


Compressor Anti Cycle
Control

Automatic via the Microprocessor.


Compressor Load Limit

Limits the condensing pressure by unloading the compressor.

Limits the evaporating pressure by unloading at the minimum pressure setpoint, which is,
adjustable depending on system glycol content.

Pump(s) Remote ON/OFF

Disables/Enables the pump(s) remotely.


Remote Setback
Temperature Setpoint
Switch

A setback setpoint for supply water temperature can be selected to suit summer/winter
conditions or night setback.


Compressor Hours Run

Displays hours run of each compressor.


Password Protection

The control system integrity can be maintained by restricting access with a password
PIN number. (as standard 4648)

CAUTION

IMPORTANT: To change the PIN number; please contact Airedale at time of order
with the preferred 4 digit number.