Glycol data, Chillers optichill freecool, Performance data – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 53

Advertising
background image

Chillers

OptiChill Freecool

Chillers

53

Technical Manual :

7197700 v1.2.0 02_2013

Performance Data

Glycol Data

For a given percentage of glycol in the system there are correction factors that need to
be applied, the following tables can be used as a guide.

CAUTION

The source data must be at 20% Glycol for the correction factors to be valid.

This data is for a guide only. Please contact Airedale for accurate figures.

Where:
Output

= (kW) Output (kW)

Compressor Input

= (kW) Input (kW), (-) Minus TFP

TFP
(Total Fan Power)

= (kW) Quantity of Fans to unit x Fan Motor Size.

Water Flow

= (l/s) ALWAYS USE 20% Glycol Specific heat Capacity of 3.9.

ΔT

= (°C) Difference of Entering Water and Leaving Water temperature

Ethylene Glycol Nominal Correction Factors

Glycol in System / Freezing
Point ºC

20% / -9°C

30% / -15°C

40% / -23°C

Cooling Duty

x by

1.00

0.98

0.96

Input Power

1.00

0.98

0.97

Water Flow

1.00

1.02

1.05

Pressure Drop

1.00

1.15

1.31

Propylene Glycol Nominal Correction Factors

Glycol in System / Freezing
Point ºC

20% / -6°C

30% / -12°C

40% / -20°C

Cooling Duty

x by

1.00

0.96

0.93

Input Power

1.00

0.98

0.97

Water Flow

1.00

0.98

0.98

Pressure Drop

1.00

1.13

1.25

Example OFC076R16-66HS1 operating at 10/15, 35°C Ambient, 30% Ethylene Glycol

Cooling kW

(752.2)

x 0.98

30% Ethylene

Glycol =

737.2 kW

Input kW

(264.7)

x 0.98

259.4 kW

Flow l/s

(38.6)

(calculated:

3.9

x

T

(Output)

)

x 1.02

39.37 l/s

Pressure Drop kPa (107.8)

x 1.15

124 kPa