Optichill freecool active cabinet exhaust chillers, Chillers, Electrical data regular quiet continued – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 76

Advertising
background image




OptiChill Freecool


Active Cabinet Exhaust

Chillers

76

Chillers

Technical Manual : 7197700 v1.2.0. 02_2013

Electrical Data Regular Quiet Continued

7

8

9

Notes

Units

OFC083R18-76ML2

OFC091R18-87HS4

OFC095R18-88MS4

Unit Data

Nominal Run Amps (1)

A

463

539

560

Maximum Start Amps

A

722

1099

905

Recommended Mains Fuse Size

A

560

670

670

Mains Supply

VAC

400 V 3 PH 50 Hz

400 V 3 PH 50 Hz

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Direct to Bus Bar

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

4 mm² terminals

4 mm² terminals

Control Circuit

VAC

24V/230VAC

24V/230VAC

24V/230VAC

Evaporator

Trace Heater Rating

W

250

250

250

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

18

18

18

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

18

18

18

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Condenser Fan - Per Fan (HAEC)

Quantity

18

18

18

Full Load Amps

A

4.5

4.5

4.5

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.86

2.86

2.86

Compressor - Per Compressor

Quantity

1 + 1

1 + 1

1 + 1

Nominal Run Amps

A

205.5 / 179.9

245.4 / 216.3

241.3 / 241.3

Motor Rating

kW

122.5 / 105.0

138.8 / 122.5

139.5 / 139.5

Sump Heater Rating

W

300

300

300

Start Amps (2)

A

465 / 436

805 / 650

586 / 586

Type Of Start

Star - Delta

Star - Delta

Star - Delta

OPTIONAL EXTRAS

Low Ambient Kit

Recommended Permanent Fuse Size

A

32

32

32

Permanent Supply

VAC

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

4 mm² terminals

4 mm² terminals

Power Factor Correction

Unit Nominal Run Amps (1)

A

423

474

501

Maximum Start Amps

A

702

1069

875

Compressor Nominal Run Amps

A

186.1 / 159.5

210.9 / 186.1

211.9 / 211.9

Recommended Mains Fuse Size

A

560

670

670

Standard Head Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

478

568

595

Recommended Mains Fuse Size

A

630

710

710

Pump Full Load Amps

A

14.8

28.5

35

Motor Rating

kW

7.5

15

18.5

Larger Head Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

491

574

601

Recommended Mains Fuse Size

A

630

710

710

Pump Full Load Amps

A

28.5

35

41.5

Motor Rating

kW

15

18.5

22

Standard Head Inverter Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

478

568

595

Recommended Mains Fuse Size

A

630

710

710

Pump Full Load Amps

A

14.8

28.5

35

Motor Rating

kW

7.5

15

18.5

Larger Head Inverter Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

491

574

601

Recommended Mains Fuse Size

A

630

710

710

Pump Full Load Amps

A

28.5

35

41.5

Motor Rating

kW

15

18.5

22

(1) Based at 5.0 Evaporating, 50 Condensing, AC Standard Fans.

(2) Starting amps refers to the Star (

Ү) connection only.