Optic hil l freec ool, Ch illers – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 22

Advertising
background image

2 Row Free Cooling Extra Quiet

AC Fans

EC Fans

HA EC Fans

Noise Variant

No. Fans

Water Temp

ΔTs

Nomenclature

Duty (kW)

EER

ESEER

2RW

Duty (kW)

EER

ESEER

2RW

Duty (kW)

EER

ESEER

2RW

X

22

H

S

OFC076X22-66HS1

757

2.86

2.84

666

754.2

3.03

3.30

654

753

3.02

3.27

650

OFC082X22-76HS2

806

2.82

2.79

678

801.9

2.98

3.21

665

801

2.97

3.19

660

OFC087X22-77HS2

850

2.78

2.79

688

845.4

2.92

3.19

674

844

2.90

3.17

669

OFC091X22-87HS4

900

2.76

2.91

698

895.1

2.88

3.32

684

894

2.87

3.30

679

OFC093X22-87HS6

925

2.81

2.85

703

920.5

2.93

3.23

689

919

2.92

3.20

684

OFC095X22-88HS4

949

2.73

2.97

708

943.9

2.84

3.37

693

942

2.83

3.35

688

OFC098X22-88HS6

978

2.78

2.92

713

972.6

2.89

3.30

698

971

2.88

3.28

693

OFC101X22-99HS5

1043

2.61

2.93

725

1036.7

2.69

3.28

709

1035

2.68

3.26

704

OFC104X22-99HS7

1078

2.67

2.96

730

1071.3

2.75

3.31

714

1069

2.73

3.29

709

L

OFC077X22-66HL1

761

2.87

2.85

667

757.7

3.04

3.31

655

757

3.03

3.28

650

OFC082X22-76HL2

810

2.84

2.81

679

806.5

2.99

3.23

666

805

2.98

3.20

661

OFC087X22-77HL2

855

2.79

2.81

689

850.8

2.93

3.21

675

849

2.92

3.18

671

OFC091X22-87HL3

904

2.77

2.92

699

899.9

2.89

3.33

685

898

2.88

3.31

680

OFC094X22-87HL5

930

2.82

2.95

704

924.7

2.94

3.36

690

923

2.93

3.34

685

OFC095X22-88HL3

954

2.74

2.98

709

949.5

2.85

3.39

694

948

2.84

3.37

689

OFC098X22-88HL5

982

2.79

3.02

714

977.0

2.90

3.42

699

975

2.89

3.40

694

OFC102X22-99HL4

1050

2.62

2.94

726

1043.5

2.71

3.29

710

1041

2.69

3.27

705

OFC105X22-99HL6

1085

2.68

2.98

731

1078.5

2.76

3.33

715

1076

2.74

3.31

710


(1) Duty (kW) based upon mechanical Cooling when the unit is configured with a 2 row free cooling coil.
(2) Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol.
(3) EER based upon mechanical Cooling when the unit is configured with a 2 row free cooling coil.
(4) ESEER based upon mechanical Cooling 12°C / 7°C 35°C Ambient.
(5) 2RW is the full free cooling potential at 3°C