Performance data, Operating limits, Typical part load characteristics – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 52: Eseer calculations, Optichill freecool active cabinet exhaust chillers

Advertising
background image




OptiChill Freecool


Active Cabinet Exhaust

Chillers

52

Chillers

Technical Manual : 7197700 v1.2.0. 02_2013

Performance Data

Operating limits

(For 100% Water)

Standard Unit

Minimum Ambient Air DB °C

-20°C

Maximum Ambient Air DB °C at Full Load Operation

35°C

Maximum Ambient Air DB °C at Reduced Load Operation

40°C

Minimum Leaving Water Temperature °C

+5°C

Maximum Return Water Temperature °C

+25°C

Minimum / Maximum

ΔT

4°K / 8°K

1

For conditions outside those quoted, please refer to Airedale.

2

For minimum ambient, it is assumed that adequate freeze protection is fitted.


Typical part load
characteristics

The following graph gives a general indication of the effect of reduced load on the
performance of the unit, for specific performance details, please contact Airedale.

%

o

f F

ul

l

Lo

a

d

EER, Coo

li

n

g

Cap

a

c

ity

a

nd

I

np

ut

1

2

3

100%

50%

0%

25%

@ 2

0

°C

A

m

b

ie

n

t

50%

@ 2

5

°C

A

m

b

ie

n

t

75%

@ 3

0

°C

A

m

b

ie

n

t

100%

@ 3

5

°C

A

m

b

ie

n

t

% of Full Load Capacity

Key

1 = EER

2 = Output kW

3 = Input kW

ESEER Calculations

The quoted EER figures cover the performance of the unit ONLY at the standard rating
conditions of 7/12°C water, 35°C ambient. The ESEER calculation method has been
developed by Eurovent to give a single value that is a realistic indication of the efficiency
of the chiller across the year round range of operation.

The ESEER value is calculated from the unit’s performance at 20, 25, 30 and 35°C
ambient temperatures for all loading stages, and with a fixed 7°C supply temperature. All
calculations assume the system operates with 100% water.

ESEER = A.EER

100%

+ B.EER

75%

+ C.EER

50%

+ D.EER

25%

A, B, C and D are weighting factors 0.03, 0.33, 0.41 and 0.23.

Temperature

20°C

25°C

30°C

35°C

Capacity Requirement

25%

50%

75%

100%

Percentage of Total Hours

0.23

0.41

0.33

0.03