Electrical data regular quiet, Optichill freecool active cabinet exhaust chillers, Chillers – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 74

Advertising
background image




OptiChill Freecool


Active Cabinet Exhaust

Chillers

74

Chillers

Technical Manual : 7197700 v1.2.0. 02_2013

Electrical Data Regular Quiet

1

2

3

Notes

Units

OFC076R16-66HS1

OFC076R16-66MS1

OFC081R16-76MS2

Unit Data

Nominal Run Amps (1)

A

447

429

454

Maximum Start Amps

A

844

685

714

Recommended Mains Fuse Size

A

560

560

560

Mains Supply

VAC

400 V 3 PH 50 Hz

400 V 3 PH 50 Hz

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Direct to Bus Bar

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

4 mm² terminals

4 mm² terminals

Control Circuit

VAC

24V/230VAC

24V/230VAC

24V/230VAC

Evaporator

Trace Heater Rating

W

250

250

250

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

16

16

16

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

16

16

16

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Condenser Fan - Per Fan (HAEC)

Quantity

16

16

16

Full Load Amps

A

4.5

4.5

4.5

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.86

2.86

2.86

Compressor - Per Compressor

Quantity

1 + 1

1 + 1

1 + 1

Nominal Run Amps

A

188.9 / 188.9

179.9 / 179.9

205.5 / 179.9

Motor Rating

kW

105.0 / 105.0

105.0 / 105.0

122.5 / 105.0

Sump Heater Rating

W

300

300

300

Start Amps (2)

A

586 / 586

436 / 436

465 / 436

Type Of Start

Star - Delta

Star - Delta

Star - Delta

OPTIONAL EXTRAS

Low Ambient Kit

Recommended Permanent Fuse Size

A

32

32

32

Permanent Supply

VAC

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

4 mm² terminals

4 mm² terminals

Power Factor Correction

Unit Nominal Run Amps (1)

A

388

388

414

Maximum Start Amps

A

814

664

693

Compressor Nominal Run Amps

A

159.5 / 159.5

159.5 / 159.5

186.1 / 159.5

Recommended Mains Fuse Size

A

560

560

560

Standard Head Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

468

457

483

Recommended Mains Fuse Size

A

560

560

630

Pump Full Load Amps

A

21.2

28.5

28.5

Motor Rating

kW

11

15

15

Larger Head Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

475

464

489

Recommended Mains Fuse Size

A

560

560

630

Pump Full Load Amps

A

28.5

35

35

Motor Rating

kW

15

18.5

18.5

Standard Head Inverter Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

468

457

483

Recommended Mains Fuse Size

A

560

560

630

Pump Full Load Amps

A

21.2

28.5

28.5

Motor Rating

kW

11

15

15

Larger Head Inverter Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

475

464

489

Recommended Mains Fuse Size

A

560

560

630

Pump Full Load Amps

A

28.5

35

35

Motor Rating

kW

15

18.5

18.5

(1) Based at 5.0 Evaporating, 50 Condensing, AC Standard Fans.

(2) Starti

ng amps refers to the Star (Ү) connection only.