Interconnecting wiring, Interconnecting, Wiring – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 118: Optichill freecool active cabinet exhaust chillers, Installation data, Chillers, Caution

Advertising
background image




OptiChill Freecool


Active Cabinet Exhaust

Chillers

118

Chillers

Technical Manual : 7197700 v1.2.0. 02_2013

Installation Data

Interconnecting Wiring

OFC

L1

Mains incoming supply 400V/3PH/50Hz

L2

L3

PE

L4

Separate Permanent Supply 230V / 1PH +N / 50Hz

N1

(1)

PE

L4

External Trace Heating Connections

N1

230V/500W max

502

(2)

Remote Pump Interlock 24VAC

507

502

(2)

Evaporator Pump Water Flow Switch 24VAC

505

502

Unit Remote On/Off 24VAC

504

502

Setback Setpoint Temperature switch

506

581

Non-

Critical

Alarm

Volt Free Common Alarm

580

Volt Free Alarm N/O

582

Volt Free Alarm N/C

591

Critical

Alarm

Volt Free Common Alarm

590

Volt Free Alarm N/O

592

Volt Free Alarm N/C

RX-/Tx-

RX+/Tx+

IN

GND

Network Connections

RX-/Tx-

RX+/Tx+

OUT

GND

CAUTION

(1) A separate permanent supply ensures that essential items such as crankcase
heaters / trace heating are energised at all times. Failure to do may cause unit
malfunction.
(2) MUST be directly wired to the chiller to validate warranty.