Chillers optichill freecool, Chillers, Mechanical data – regular quiet continued – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 61

Advertising
background image

Chillers

OptiChill Freecool

Chillers

61

Technical Manual :

7197700 v1.2.0 02_2013

Mechanical Data

– Regular Quiet Continued

15

16

Notes

Units

OFC108R20-99HL6

OFC078R22-66MS1

2 Row Free Cool

3 Row Free Cool

2 Row Free Cool

3 Row Free Cool

Cooling Duty - AC Fans

1

kW

1110.7

1103

777.7

774.4

Nom Input -Cooling Only

kW

399.1

403.3

267.8

269.9

EER

2

2.78

2.73

2.9

2.87

ESEER

7

3.01

2.96

2.94

2.9

SEER

7

2.97

2.93

2.92

2.88

Nominal Output - Free Cooling

5

kW

764.6

866.9

744.5

829.5

Ambient when Free Cooling = 100% Nominal DX

6

°C

-2.4

-0.3

2.5

3.8

Cooling Duty - EC Fans

1

kW

1117.3

1113

765.2

762.3

Nom Input -Cooling Only

kW

394.2

398.9

251.7

254.5

EER

2

2.83

2.79

3.04

3

ESEER

7

3.31

3.26

3.41

3.36

SEER

7

3.24

3.19

3.35

3.3

Nominal Output - Free Cooling

5

kW

798

911.7

765

854.5

Ambient when Free Cooling = 100% Nominal DX

6

°C

-1.8

0.4

3

4.3

Cooling Duty - High Airflow EC Fans

1

kW

1116.3

1111.8

765.6

762.7

Nom Input -Cooling Only

kW

394.3

399

252.2

254.9

EER

2

2.83

2.79

3.04

2.99

ESEER

7

3.3

3.24

3.38

3.33

SEER

7

3.23

3.18

3.32

3.27

Nominal Output - Free Cooling

5

kW

825.3

947

786

879.5

Ambient when Free Cooling = 100% Nominal DX

6

°C

-1.2

0.9

3.3

4.6

Capacity Steps

%

20, 30, 40, 55, 65, 80, 90, 100

Dimensions (H x W x L)

mm

2600 x 2200 x 11850

2600 x 2200 x 12850

Machine Weight

kg

13910

13985

13900

14000

Operating Weight

3

kg

15890

16115

15660

15920

Construction Material

Base: Plain Galvanised Steel, Panels: Galvanised Sheet Steel, Epoxy Baked

Powder Paint, Light Grey (RAL 7035)

Evaporator - Type

Shell and Tube

Insulation

Class O / UV Stable

Total Max. Water Flow

l/s

91.9

91.9

72.8

72.8

Total Min. Water Flow

l/s

22.8

22.8

18.1

18.1

Condenser - Type

Rifled Copper Tube / Aluminium Fin

Face Area Total

39.6

39.6

43.6

43.6

Maximum Airflow - High Airflow EC Fans

m³/s

106.1

101.5

116.7

111.6

Maximum Airflow - EC Fans

m³/s

99

94.5

108.9

104

Maximum Airflow - AC Fans

m³/s

90.7

86.1

99.7

94.8

Condenser Fan & Motor

Sickle Bladed Axial Fan

Quantity

20

20

22

22

Diameter

mm

800

800

800

800

Maximum Speed - High Airflow EC Fans

RPM

1080

1080

1080

1080

Maximum Speed - EC Fans

RPM

980

980

980

980

Maximum Speed - AC Fans

RPM

900

900

900

900

Compressor - Type

Semi-Hermetic Twin Screw Compressor

Quantity

2

2

2

2

Oil Charge Volume (Total)

l

35 + 35

35 + 35

35 + 35

35 + 35

Oil Type

BSE 170 Polyol Ester Oil

Refrigerant - Control

Electronic Expansion Valve

Refrigerant Pre-charged

R134a

Charge (Total) CCT1 + CCT2

kg

208 + 209

208 + 209

191 + 192

191 + 192

Water Connections

Type

Grooved Terminations

Inlet / Outlet - Unit

DN200

DN200

DN200

DN200

Water Drain / Bleed - Evap

inch

0.5

0.5

0.5

0.5

Water System - Volume

l

1977

2125

1756

1919

Minimum System Water Volume

4

l

5416

5553

4055

4212

Max System Operating Pressure

Bar

10

10

10

10

Flow Rate 20% Ethylene Glycol

l/s

59.8

59.4

41.9

41.7

Pressure Drop 20% Ethylene Glycol

kPa

177.6

141.5

106.6

85.8

(1) Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol.
(2) EER = DX Cooling Output / (Compressor Input Power + Fan Input Power)
(3) Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options fitted please refer to Airedale.
(4) For minimum system water volume calculation, refer to Design Features & Information - Minimum System Water Volume Calculations.
(5) Nominal Free Cooling Output at 15/10°C return/supply temperatures, 3°C ambient, 20% Ethylene Glycol.
(6) Ambient temperature that Maximum Nominal DX Duty can be achieved using Free Cooling only.
(7) ESEER / SEER based upon unit operating at 12 / 7 °C return / supply temperature, 35°C ambient,

Advertising