Pump packages (optional extras), Optichill freecool active cabinet exhaust chillers, Performance data – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 98

Advertising
background image




OptiChill Freecool


Active Cabinet Exhaust

Chillers

98

Chillers

Technical Manual : 7197700 v1.2.0. 02_2013

Performance Data

Pump packages (optional extras)

CAUTION

Full design water flow MUST be maintained at all times. Variable water volume is
NOT recommended and will invalidate warranty.

Use the formula below and the graphs provided to calculate the External Head Available:

Example

Model Ref.

= OFC084R20-76HL2

Ambient:

= 35°C

Fluid

= 100% Water

Inlet Fluid Temp.

= 15°C

Outlet Fluid Temp.

= 10°C (5°K

T)

Pump Selection

= Single Standard Head - Standard ac Motor - Fixed Speed Option

Fluid Flow l/s

= 42.3 l/s

EHA (kPa) =

External Head Available

EHA (kPa) =

Total Pump Head Available

-

Unit Waterside Pressure Drop

EHA (kPa) =

123 - 33

EHA (kPa) =

90 kPa

Pump Curve

Pump Curve

Regular Quiet

50 kPa

100 kPa

Extra Quiet

50 kPa

100 kPa

1

OFC076R16-66HS1

65-4

80-2

21

OFC073X16-66HS1

65-6

80-2

2

OFC076R16-66MS1

80-2

80-3

22

OFC074X16-66HL1

65-5

65-5

3

OFC081R16-76MS2

80-2

80-3

23

OFC078X16-76HS2

65-4

80-2

4

OFC081R16-76ML2

65-5

80-2

24

OFC079X16-76HL2

65-5

65-5

5

OFC087R16-77ML2

65-5

80-2

25

OFC083X16-77HL2

65-5

65-6

6

OFC077R18-66HS1

65-4

80-2

26

OFC075X18-66MS1

65-8

80-2

7

OFC083R18-76ML2

65-5

80-2

27

OFC080X18-76ML2

65-5

80-2

8

OFC091R18-87HS4

80-2

80-3

28

OFC088X18-87HS4

80-2

80-3

9

OFC095R18-88MS4

80-3

80-4

29

OFC095X18-88HS6

80-2

80-3

10

OFC107R18-99HL5

65-4

80-2

30

OFC102X18-99HL6

65-6

65-6

11

OFC078R20-66ML1

65-5

65-5

31

OFC076X20-66HS1

65-4

80-2

12

OFC084R20-76HL2

65-5

65-5

32

OFC081X20-76ML2

65-5

80-2

13

OFC092R20-87MS4

80-3

80-4

33

OFC092X20-87HS6

80-2

80-3

14

OFC099R20-88HS6

80-2

80-3

34

OFC097X20-88HL5

65-6

80-2

15

OFC108R20-99HL6

65-4

80-2

35

OFC104X20-99HL6

65-3

80-2

16

OFC078R22-66MS1

80-2

80-3

36

OFC076X22-66HS1

65-4

80-2

17

OFC084R22-76MS2

80-2

80-3

37

OFC082X22-76ML2

65-5

80-2

18

OFC093R22-87HS4

80-2

80-3

38

OFC091X22-87HS4

80-2

80-3

19

OFC097R22-88MS4

80-3

80-5

39

OFC093X22-87ML5

65-6

80-2

20

OFC109R22-99HL5

65-4

80-2

40

OFC105X22-99HL6

65-4

80-2


(1) Pump curves correspond to available external head available.

Pump Code

Airedale Code

65-125/120-110-2-50

65-1

65-125/127-2-50

65- 2

65-125/137-2-50

65- 3

65-125/144-2-50

65- 4

65-160/143-2-50

65- 5

65-160/157-2-50

65- 6

65-160/173-2-50

65- 7

65-160/177-2-50

65- 8

80-160/147-127-2-50

80-1

80-160/151-2-50

80- 2

80-160/161-2-50

80- 3

80-160/167-2-50

80- 4

80-160/177-2-50

80- 5

Advertising