Technical Manual :

7197700 v1.2.0 02_2013

Electrical Data Regular Quiet Continued

4

5

6

Notes

Units

OFC081R16-76ML2

OFC087R16-77ML2

OFC077R18-66HS1

Unit Data

Nominal Run Amps (1)

A

454

480

455

Maximum Start Amps

A

714

739

852

Recommended Mains Fuse Size

A

560

630

560

Mains Supply

VAC

400 V 3 PH 50 Hz

400 V 3 PH 50 Hz

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Direct to Bus Bar

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

4 mm² terminals

4 mm² terminals

Control Circuit

VAC

24V/230VAC

24V/230VAC

24V/230VAC

Evaporator

Trace Heater Rating

W

250

250

250

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

16

16

18

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

16

16

18

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Condenser Fan - Per Fan (HAEC)

Quantity

16

16

18

Full Load Amps

A

4.5

4.5

4.5

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.86

2.86

2.86

Compressor - Per Compressor

Quantity

1 + 1

1 + 1

1 + 1

Nominal Run Amps

A

205.5 / 179.9

205.5 / 205.5

188.9 / 188.9

Motor Rating

kW

122.5 / 105.0

122.5 / 122.5

105.0 / 105.0

Sump Heater Rating

W

300

300

300

Start Amps (2)

A

465 / 436

465 / 465

586 / 586

Type Of Start

Star - Delta

Star - Delta

Star - Delta

OPTIONAL EXTRAS

Low Ambient Kit

Recommended Permanent Fuse Size

A

32

32

32

Permanent Supply

VAC

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

4 mm² terminals

4 mm² terminals

Power Factor Correction

Unit Nominal Run Amps (1)

A

414

441

396

Maximum Start Amps

A

693

720

823

Compressor Nominal Run Amps

A

186.1 / 159.5

186.1 / 186.1

159.5 / 159.5

Recommended Mains Fuse Size

A

560

630

560

Standard Head Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

469

495

476

Recommended Mains Fuse Size

A

630

630

630

Pump Full Load Amps

A

14.8

14.8

21.2

Motor Rating

kW

7.5

7.5

11

Larger Head Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

483

508

484

Recommended Mains Fuse Size

A

630

630

630

Pump Full Load Amps

A

28.5

28.5

28.5

Motor Rating

kW

15

15

15

Standard Head Inverter Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

469

495

476

Recommended Mains Fuse Size

A

630

630

630

Pump Full Load Amps

A

14.8

14.8

21.2

Motor Rating

kW

7.5

7.5

11

Larger Head Inverter Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

483

508

484

Recommended Mains Fuse Size

A

630

630

630

Pump Full Load Amps

A

28.5

28.5

28.5

Motor Rating

kW

15

15

15

(1) Based at 5.0 Evaporating, 50 Condensing, AC Standard Fans.

(2) Starting amps refers to the Star (

Ү) connection only.