Electrical Data Regular Quiet Continued

16

17

18

Notes

Units

OFC078R22-66MS1

OFC084R22-76MS2

OFC093R22-87HS4

Unit Data

Nominal Run Amps (1)

A

454

480

556

Maximum Start Amps

A

711

740

1116

Recommended Mains Fuse Size

A

560

630

670

Mains Supply

VAC

400 V 3 PH 50 Hz

400 V 3 PH 50 Hz

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Direct to Bus Bar

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

4 mm² terminals

4 mm² terminals

Control Circuit

VAC

24V/230VAC

24V/230VAC

24V/230VAC

Evaporator

Trace Heater Rating

W

250

250

250

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

22

22

22

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

22

22

22

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Condenser Fan - Per Fan (HAEC)

Quantity

22

22

22

Full Load Amps

A

4.5

4.5

4.5

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.86

2.86

2.86

Compressor - Per Compressor

Quantity

1 + 1

1 + 1

1 + 1

Nominal Run Amps

A

179.9 / 179.9

205.5 / 179.9

245.4 / 216.3

Motor Rating

kW

105.0 / 105.0

122.5 / 105.0

138.8 / 122.5

Sump Heater Rating

W

300

300

300

Start Amps (2)

A

436 / 436

465 / 436

805 / 650

Type Of Start

Star - Delta

Star - Delta

Star - Delta

OPTIONAL EXTRAS

Low Ambient Kit

Recommended Permanent Fuse Size

A

32

32

32

Permanent Supply

VAC

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

4 mm² terminals

4 mm² terminals

Power Factor Correction

Unit Nominal Run Amps (1)

A

414

440

492

Maximum Start Amps

A

690

719

1086

Compressor Nominal Run Amps

A

159.5 / 159.5

186.1 / 159.5

210.9 / 186.1

Recommended Mains Fuse Size

A

560

630

670

Standard Head Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

483

509

585

Recommended Mains Fuse Size

A

630

630

710

Pump Full Load Amps

A

28.5

28.5

28.5

Motor Rating

kW

15

15

15

Larger Head Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

489

515

591

Recommended Mains Fuse Size

A

630

630

710

Pump Full Load Amps

A

35

35

35

Motor Rating

kW

18.5

18.5

18.5

Standard Head Inverter Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

483

509

585

Recommended Mains Fuse Size

A

630

630

710

Pump Full Load Amps

A

28.5

28.5

28.5

Motor Rating

kW

15

15

15

Larger Head Inverter Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

489

515

591

Recommended Mains Fuse Size

A

630

630

710

Pump Full Load Amps

A

35

35

35

Motor Rating

kW

18.5

18.5

18.5

(1) Based at 5.0 Evaporating, 50 Condensing, AC Standard Fans.

(2) Starting amps refers to the Star (

Ү) connection only.