Optichill freecool active cabinet exhaust chillers, Chillers, Mechanical data - extra quiet continued – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 66

Advertising
background image




OptiChill Freecool


Active Cabinet Exhaust

Chillers

66

Chillers

Technical Manual : 7197700 v1.2.0. 02_2013

Mechanical Data - Extra Quiet Continued

25

26

Notes

Units

OFC083X16-77HL2

OFC075X18-66MS1

2 Row Free Cool

3 Row Free Cool

2 Row Free Cool

3 Row Free Cool

Cooling Duty - AC Fans

1

kW

815.8

807.8

741.8

736.1

Nom Input -Cooling Only

kW

313.8

317.8

268.1

271.1

EER

2

2.6

2.54

2.77

2.71

ESEER

7

2.76

2.72

2.9

2.85

SEER

7

2.73

2.69

2.87

2.82

Nominal Output - Free Cooling

5

kW

513.1

567

556.7

612.9

Ambient when Free Cooling = 100% Nominal DX

6

°C

-4.1

-2.1

-1

0.6

Cooling Duty - EC Fans

1

kW

809.7

801.2

737.5

731.5

Nom Input -Cooling Only

kW

303.7

307.8

255.6

258.7

EER

2

2.67

2.6

2.89

2.83

ESEER

7

3.05

2.99

3.29

3.23

SEER

7

2.99

2.94

3.23

3.17

Nominal Output - Free Cooling

5

kW

502.2

553.2

545.6

599.1

Ambient when Free Cooling = 100% Nominal DX

6

°C

-4.3

-2.4

-1.2

0.4

Cooling Duty - High Airflow EC Fans

1

kW

807.7

798.9

736.1

729.8

Nom Input -Cooling Only

kW

304.6

308.8

256.3

259.4

EER

2

2.65

2.59

2.87

2.81

ESEER

7

3.03

2.98

3.27

3.21

SEER

7

2.98

2.92

3.21

3.15

Nominal Output - Free Cooling

5

kW

498.6

548.4

542

594.3

Ambient when Free Cooling = 100% Nominal DX

6

°C

-4.4

-2.5

-1.3

0.3

Capacity Steps

%

20, 30, 40, 55, 65, 80, 90, 100

Dimensions (H x W x L)

mm

2600 x 2200 x 9850

2600 x 2200 x 10850

Machine Weight

kg

11325

11395

12435

12510

Operating Weight

3

kg

12555

12745

13965

14170

Construction Material

Base: Plain Galvanised Steel, Panels: Galvanised Sheet Steel, Epoxy Baked

Powder Paint, Light Grey (RAL 7035)

Evaporator - Type

Shell and Tube

Insulation

Class O / UV Stable

Total Max. Water Flow

l/s

58.1

58.1

72.8

72.8

Total Min. Water Flow

l/s

14.4

14.4

18.1

18.1

Condenser - Type

Rifled Copper Tube / Aluminium Fin

Face Area Total

31.7

31.7

35.6

35.6

Maximum Airflow - High Airflow EC Fans

m³/s

N/A

N/A

N/A

N/A

Maximum Airflow - EC Fans

m³/s

55.3

52.6

62.2

59.2

Maximum Airflow - AC Fans

m³/s

54.1

50.7

60.9

57.1

Condenser Fan & Motor

Sickle Bladed Axial Fan

Quantity

16

16

18

18

Diameter

mm

800

800

800

800

Maximum Speed - High Airflow EC Fans

RPM

N/A

N/A

N/A

N/A

Maximum Speed - EC Fans

RPM

700

700

700

700

Maximum Speed - AC Fans

RPM

700

700

700

700

Compressor - Type

Semi-Hermetic Twin Screw Compressor

Quantity

2

2

2

2

Oil Charge Volume (Total)

l

35 + 35

35 + 35

35 + 35

35 + 35

Oil Type

BSE 170 Polyol Ester Oil

Refrigerant - Control

Electronic Expansion Valve

Refrigerant Pre-charged

R134a

Charge (Total) CCT1 + CCT2

kg

156 + 157

156 + 157

167 + 168

167 + 168

Water Connections

Type

Grooved Terminations

Inlet / Outlet - Unit

DN150

DN150

DN200

DN200

Water Drain / Bleed - Evap

inch

0.5

0.5

0.5

0.5

Water System - Volume

l

1228

1346

1532

1665

Minimum System Water Volume

4

l

3469

3580

3834

3960

Max System Operating Pressure

Bar

10

10

10

10

Flow Rate 20% Ethylene Glycol

l/s

43.9

43.5

39.9

39.6

Pressure Drop 20% Ethylene Glycol

kPa

177.7

158.8

91

74.8

(1) Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol.
(2) EER = DX Cooling Output / (Compressor Input Power + Fan Input Power)
(3) Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options fitted please refer to Airedale.
(4) For minimum system water volume calculation, refer to Design Features & Information - Minimum System Water Volume Calculations.
(5) Nominal Free Cooling Output at 15/10°C return/supply temperatures, 3°C ambient, 20% Ethylene Glycol.
(6) Ambient temperature that Maximum Nominal DX Duty can be achieved using Free Cooling only.
(7) ESEER / SEER based upon unit operating at 12 / 7 °C return / supply temperature, 35°C ambient,

Advertising