Installation Data

Unit Lifting

Employ lifting specialists

Local codes and regulations relating to the lifting of this type of equipment should
be observed

Use the appropriate spreader bars/lifting slings (provided by others) with the
holes/lugs provided

Attach individual lifting chains to each of the lifting eye bolts/lifting lugs provided;
each individual chain must be capable of lifting the whole unit

IMPORTANT

Do not use 1 chain between 2 lifting points to avoid load shift.

Only use lifting points provided.

Lifting hole/lug dimension: 40mm

Chains/slings MUST NOT interfere with the casing or fan assembly to avoid damage

Lift the unit slowly and evenly

IMPORTANT

If the unit is dropped, it should immediately be checked for damage and reported
to Airedale.

Lifting Dimensions

A1 (Min)

A2 (Min)

B

C

16 FAN

mm

5000

5000

520

5000

18 FAN

mm

6000

5000

520

5650

20 FAN

mm

7000

5000

520

6650

22 FAN

mm

7000

5000

520

6650

IMPORTANT

For models with optional pumps fitted, a separate instruction will be provided.