Optichill freecool active cabinet exhaust chillers, Chillers, Electrical data extra quiet continued – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 84

Advertising
background image




OptiChill Freecool


Active Cabinet Exhaust

Chillers

84

Chillers

Technical Manual : 7197700 v1.2.0. 02_2013

Electrical Data Extra Quiet Continued

30

31

32

Notes

Units

OFC102X18-99HL6

OFC076X20-66HS1

OFC081X20-76ML2

Unit Data

Nominal Run Amps (1)

A

577

428

435

Maximum Start Amps

A

1116

825

695

Recommended Mains Fuse Size

A

710

560

560

Mains Supply

VAC

400 V 3 PH 50 Hz

400 V 3 PH 50 Hz

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Direct to Bus Bar

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

4 mm² terminals

4 mm² terminals

Control Circuit

VAC

24V/230VAC

24V/230VAC

24V/230VAC

Evaporator

Trace Heater Rating

W

250

250

250

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

18

20

20

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.27

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

18

20

20

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Condenser Fan - Per Fan (HAEC)

Quantity

18

20

20

Full Load Amps

A

4.5

4.5

4.5

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.86

2.86

2.86

Compressor - Per Compressor

Quantity

1 + 1

1 + 1

1 + 1

Nominal Run Amps

A

266.2 / 266.2

188.9 / 188.9

205.5 / 179.9

Motor Rating

kW

152.7 / 152.7

105.0 / 105.0

122.5 / 105.0

Sump Heater Rating

W

300

300

300

Start Amps (2)

A

805 / 805

586 / 586

465 / 436

Type Of Start

Star - Delta

Star - Delta

Star - Delta

OPTIONAL EXTRAS

Low Ambient Kit

Recommended Permanent Fuse Size

A

32

32

32

Permanent Supply

VAC

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

4 mm² terminals

4 mm² terminals

Power Factor Correction

Unit Nominal Run Amps (1)

A

509

369

396

Maximum Start Amps

A

1082

796

675

Compressor Nominal Run Amps

A

232.0 / 232.0

159.5 / 159.5

186.1 / 159.5

Recommended Mains Fuse Size

A

710

560

560

Standard Head Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

599

449

450

Recommended Mains Fuse Size

A

750

560

560

Pump Full Load Amps

A

21.2

21.2

14.8

Motor Rating

kW

11

11

7.5

Larger Head Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

599

456

464

Recommended Mains Fuse Size

A

800

560

560

Pump Full Load Amps

A

21.2

28.5

28.5

Motor Rating

kW

11

15

15

Standard Head Inverter Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

599

449

450

Recommended Mains Fuse Size

A

750

560

560

Pump Full Load Amps

A

21.2

21.2

14.8

Motor Rating

kW

11

11

7.5

Larger Head Inverter Pump (Single or Run/Standby)

Unit Nominal Run Amps

A

599

456

464

Recommended Mains Fuse Size

A

800

560

560

Pump Full Load Amps

A

21.2

28.5

28.5

Motor Rating

kW

11

15

15

(1) Based at 5.0 Evaporating, 50 Condensing, AC Standard Fans.

(2) Starting amps refers to the Star (

Ү) connection only.

Advertising
This manual is related to the following products: