Chillers

Technical Manual : 7197700 v1.2.0. 02_2013

Mechanical Data - Extra Quiet Continued

33

34

Notes

Units

OFC092X20-87HS6

OFC097X20-88HL5

2 Row Free Cool

3 Row Free Cool

2 Row Free Cool

3 Row Free Cool

Cooling Duty - AC Fans

1

kW

913.8

906.4

969.7

961.6

Nom Input -Cooling Only

kW

331.6

335.4

354.6

358.9

EER

2

2.76

2.7

2.73

2.68

ESEER

7

2.84

2.79

3.01

2.96

SEER

7

2.81

2.77

2.96

2.91

Nominal Output - Free Cooling

5

kW

644.5

715.2

653.9

727.1

Ambient when Free Cooling = 100% Nominal DX

6

°C

-2

-0.2

-2.8

-0.9

Cooling Duty - EC Fans

1

kW

908.3

900.4

963.6

954.9

Nom Input -Cooling Only

kW

318.1

322

341.5

345.9

EER

2

2.86

2.8

2.82

2.76

ESEER

7

3.18

3.12

3.37

3.31

SEER

7

3.13

3.07

3.3

3.24

Nominal Output - Free Cooling

5

kW

630.8

697.9

639.8

709.2

Ambient when Free Cooling = 100% Nominal DX

6

°C

-2.3

-0.5

-3.1

-1.2

Cooling Duty - High Airflow EC Fans

1

kW

906.4

898.2

961.5

952.5

Nom Input -Cooling Only

kW

318.9

322.9

342.5

347

EER

2

2.84

2.78

2.81

2.75

ESEER

7

3.16

3.1

3.35

3.29

SEER

7

3.11

3.06

3.28

3.22

Nominal Output - Free Cooling

5

kW

626.4

692

635.2

703

Ambient when Free Cooling = 100% Nominal DX

6

°C

-2.4

-0.6

-3.2

-1.3

Capacity Steps

%

20, 30, 40, 55, 65, 80, 90, 100

Dimensions (H x W x L)

mm

2600 x 2200 x 11850

2600 x 2200 x 11850

Machine Weight

kg

13780

13870

13850

13935

Operating Weight

3

kg

15780

16010

15840

16075

Construction Material

Base: Plain Galvanised Steel, Panels: Galvanised Sheet Steel, Epoxy Baked

Powder Paint, Light Grey (RAL 7035)

Evaporator - Type

Shell and Tube

Insulation

Class O / UV Stable

Total Max. Water Flow

l/s

91.9

91.9

73.3

73.3

Total Min. Water Flow

l/s

22.8

22.8

18.1

18.1

Condenser - Type

Rifled Copper Tube / Aluminium Fin

Face Area Total

39.6

39.6

39.6

39.6

Maximum Airflow - High Airflow EC Fans

m³/s

N/A

N/A

N/A

N/A

Maximum Airflow - EC Fans

m³/s

69.1

65.7

69.1

65.7

Maximum Airflow - AC Fans

m³/s

67.7

63.4

67.7

63.4

Condenser Fan & Motor

Sickle Bladed Axial Fan

Quantity

20

20

20

20

Diameter

mm

800

800

800

800

Maximum Speed - High Airflow EC Fans

RPM

N/A

N/A

N/A

N/A

Maximum Speed - EC Fans

RPM

700

700

700

700

Maximum Speed - AC Fans

RPM

700

700

700

700

Compressor - Type

Semi-Hermetic Twin Screw Compressor

Quantity

2

2

2

2

Oil Charge Volume (Total)

l

35 + 35

35 + 35

35 + 35

35 + 35

Oil Type

BSE 170 Polyol Ester Oil

Refrigerant - Control

Electronic Expansion Valve

Refrigerant Pre-charged

R134a

Charge (Total) CCT1 + CCT2

kg

205 + 198

205 + 198

205 + 207

205 + 207

Water Connections

Type

Grooved Terminations

Inlet / Outlet - Unit

DN200

DN200

DN200

DN200

Water Drain / Bleed - Evap

inch

0.5

0.5

0.5

0.5

Water System - Volume

l

1992

2140

1992

2140

Minimum System Water Volume

4

l

5013

5152

5026

5164

Max System Operating Pressure

Bar

10

10

10

10

Flow Rate 20% Ethylene Glycol

l/s

49.2

48.8

52.2

51.8

Pressure Drop 20% Ethylene Glycol

kPa

122.4

96.6

177.9

148.6

(1) Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol.
(2) EER = DX Cooling Output / (Compressor Input Power + Fan Input Power)
(3) Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options fitted please refer to Airedale.
(4) For minimum system water volume calculation, refer to Design Features & Information - Minimum System Water Volume Calculations.
(5) Nominal Free Cooling Output at 15/10°C return/supply temperatures, 3°C ambient, 20% Ethylene Glycol.
(6) Ambient temperature that Maximum Nominal DX Duty can be achieved using Free Cooling only.
(7) ESEER / SEER based upon unit operating at 12 / 7 °C return / supply temperature, 35°C ambient.