Mechanical Data - Extra Quiet Continued

29

30

Notes

Units

OFC095X18-88HS6

OFC102X18-99HL6

2 Row Free Cool

3 Row Free Cool

2 Row Free Cool

3 Row Free Cool

Cooling Duty - AC Fans

1

kW

948.9

939.8

1048.5

1037

Nom Input -Cooling Only

kW

358.6

363.4

416.8

422.9

EER

2

2.65

2.59

2.52

2.45

ESEER

7

2.89

2.83

2.93

2.87

SEER

7

2.85

2.8

2.87

2.82

Nominal Output - Free Cooling

5

kW

591.6

657.3

605

673.9

Ambient when Free Cooling = 100% Nominal DX

6

°C

-4.2

-2.2

-5.8

-3.5

Cooling Duty - EC Fans

1

kW

942.1

932.4

1039.8

1027.6

Nom Input -Cooling Only

kW

347.4

352.4

406.6

412.9

EER

2

2.71

2.65

2.56

2.49

ESEER

7

3.18

3.12

3.2

3.13

SEER

7

3.12

3.06

3.12

3.05

Nominal Output - Free Cooling

5

kW

578.6

640.8

591.2

656.3

Ambient when Free Cooling = 100% Nominal DX

6

°C

-4.5

-2.5

-6.1

-3.8

Cooling Duty - High Airflow EC Fans

1

kW

939.8

929.7

1036.9

1024.2

Nom Input -Cooling Only

kW

348.5

353.6

408.1

414.5

EER

2

2.7

2.63

2.54

2.47

ESEER

7

3.16

3.1

3.18

3.12

SEER

7

3.1

3.04

3.1

3.04

Nominal Output - Free Cooling

5

kW

574.4

635.1

586.7

650.3

Ambient when Free Cooling = 100% Nominal DX

6

°C

-4.6

-2.6

-6.2

-3.9

Capacity Steps

%

20, 30, 40, 55, 65, 80, 90, 100

Dimensions (H x W x L)

mm

2600 x 2200 x 10850

2600 x 2200 x 10850

Machine Weight

kg

13130

13195

13200

13285

Operating Weight

3

kg

15020

15225

15070

15285

Construction Material

Base: Plain Galvanised Steel, Panels: Galvanised Sheet Steel, Epoxy Baked

Powder Paint, Light Grey (RAL 7035)

Evaporator - Type

Shell and Tube

Insulation

Class O / UV Stable

Total Max. Water Flow

l/s

91.9

91.9

91.9

91.9

Total Min. Water Flow

l/s

22.8

22.8

22.8

22.8

Condenser - Type

Rifled Copper Tube / Aluminium Fin

Face Area Total

35.6

35.6

35.6

35.6

Maximum Airflow - High Airflow EC Fans

m³/s

N/A

N/A

N/A

N/A

Maximum Airflow - EC Fans

m³/s

62.2

59.2

62.2

59.2

Maximum Airflow - AC Fans

m³/s

60.9

57.1

60.9

57.1

Condenser Fan & Motor

Sickle Bladed Axial Fan

Quantity

18

18

18

18

Diameter

mm

800

800

800

800

Maximum Speed - High Airflow EC Fans

RPM

N/A

N/A

N/A

N/A

Maximum Speed - EC Fans

RPM

700

700

700

700

Maximum Speed - AC Fans

RPM

700

700

700

700

Compressor - Type

Semi-Hermetic Twin Screw Compressor

Quantity

2

2

2

2

Oil Charge Volume (Total)

l

35 + 35

35 + 35

35 + 35

35 + 35

Oil Type

BSE 170 Polyol Ester Oil

Refrigerant - Control

Electronic Expansion Valve

Refrigerant Pre-charged

R134a

Charge (Total) CCT1 + CCT2

kg

197 + 196

197 + 196

199 + 198

199 + 198

Water Connections

Type

Grooved Terminations

Inlet / Outlet - Unit

DN200

DN200

DN200

DN200

Water Drain / Bleed - Evap

inch

0.5

0.5

0.5

0.5

Water System - Volume

l

1889

2022

1874

2007

Minimum System Water Volume

4

l

4912

5035

5314

5437

Max System Operating Pressure

Bar

10

10

10

10

Flow Rate 20% Ethylene Glycol

l/s

51.1

50.6

56.4

55.8

Pressure Drop 20% Ethylene Glycol

kPa

125.7

100.5

153.5

123.1

(1) Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol.
(2) EER = DX Cooling Output / (Compressor Input Power + Fan Input Power)
(3) Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options fitted please refer to Airedale.
(4) For minimum system water volume calculation, refer to Design Features & Information - Minimum System Water Volume Calculations.
(5) Nominal Free Cooling Output at 15/10°C return/supply temperatures, 3°C ambient, 20% Ethylene Glycol.
(6) Ambient temperature that Maximum Nominal DX Duty can be achieved using Free Cooling only.