Chillers optichill freecool, Chillers, Mechanical data - extra quiet continued – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 67

Advertising
background image

Chillers

OptiChill Freecool

Chillers

67

Technical Manual :

7197700 v1.2.0 02_2013

Mechanical Data - Extra Quiet Continued

27

28

Notes

Units

OFC080X18-76ML2

OFC088X18-87HS4

2 Row Free Cool

3 Row Free Cool

2 Row Free Cool

3 Row Free Cool

Cooling Duty - AC Fans

1

kW

795.9

789.2

875.4

867.7

Nom Input -Cooling Only

kW

287.4

290.7

331.9

336.1

EER

2

2.77

2.72

2.64

2.58

ESEER

7

2.89

2.84

2.89

2.84

SEER

7

2.87

2.82

2.85

2.8

Nominal Output - Free Cooling

5

kW

566.8

625.7

580.4

643.1

Ambient when Free Cooling = 100% Nominal DX

6

°C

-1.8

-0.1

-3.1

-1.2

Cooling Duty - EC Fans

1

kW

790.8

783.7

869.6

861.5

Nom Input -Cooling Only

kW

275.1

278.5

320.3

324.6

EER

2

2.88

2.82

2.72

2.66

ESEER

7

3.25

3.19

3.21

3.16

SEER

7

3.2

3.14

3.15

3.09

Nominal Output - Free Cooling

5

kW

555.1

611.1

568

627.4

Ambient when Free Cooling = 100% Nominal DX

6

°C

-2.1

-0.4

-3.4

-1.5

Cooling Duty - High Airflow EC Fans

1

kW

789.2

781.8

867.7

859.3

Nom Input -Cooling Only

kW

275.8

279.3

321.2

325.6

EER

2

2.86

2.8

2.7

2.64

ESEER

7

3.23

3.18

3.2

3.14

SEER

7

3.18

3.12

3.13

3.07

Nominal Output - Free Cooling

5

kW

551.3

606

563.9

622

Ambient when Free Cooling = 100% Nominal DX

6

°C

-2.2

-0.5

-3.5

-1.6

Capacity Steps

%

20, 30, 40, 55, 65, 80, 90, 100

Dimensions (H x W x L)

mm

2600 x 2200 x 10850

2600 x 2200 x 10850

Machine Weight

kg

11620

11675

11770

11850

Operating Weight

3

kg

13980

14185

14175

14380

Construction Material

Base: Plain Galvanised Steel, Panels: Galvanised Sheet Steel, Epoxy Baked

Powder Paint, Light Grey (RAL 7035)

Evaporator - Type

Shell and Tube

Insulation

Class O / UV Stable

Total Max. Water Flow

l/s

58.1

58.1

79.2

79.2

Total Min. Water Flow

l/s

14.4

14.4

19.7

19.7

Condenser - Type

Rifled Copper Tube / Aluminium Fin

Face Area Total

35.6

35.6

35.6

35.6

Maximum Airflow - High Airflow EC Fans

m³/s

N/A

N/A

N/A

N/A

Maximum Airflow - EC Fans

m³/s

62.2

59.2

62.2

59.2

Maximum Airflow - AC Fans

m³/s

60.9

57.1

60.9

57.1

Condenser Fan & Motor

Sickle Bladed Axial Fan

Quantity

18

18

18

18

Diameter

mm

800

800

800

800

Maximum Speed - High Airflow EC Fans

RPM

N/A

N/A

N/A

N/A

Maximum Speed - EC Fans

RPM

700

700

700

700

Maximum Speed - AC Fans

RPM

700

700

700

700

Compressor - Type

Semi-Hermetic Twin Screw Compressor

Quantity

2

2

2

2

Oil Charge Volume (Total)

l

35 + 35

35 + 35

35 + 35

35 + 35

Oil Type

BSE 170 Polyol Ester Oil

Refrigerant - Control

Electronic Expansion Valve

Refrigerant Pre-charged

R134a

Charge (Total) CCT1 + CCT2

kg

169 + 170

169 + 170

180 + 173

180 + 173

Water Connections

Type

Grooved Terminations

Inlet / Outlet - Unit

DN200

DN200

DN200

DN200

Water Drain / Bleed - Evap

inch

0.5

0.5

0.5

0.5

Water System - Volume

l

1520

1653

1554

1687

Minimum System Water Volume

4

l

3851

3976

4572

4695

Max System Operating Pressure

Bar

10

10

10

10

Flow Rate 20% Ethylene Glycol

l/s

42.8

42.5

47.1

46.7

Pressure Drop 20% Ethylene Glycol

kPa

141.3

122.3

121.4

99.5

(1) Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol.
(2) EER = DX Cooling Output / (Compressor Input Power + Fan Input Power)
(3) Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options fitted please refer to Airedale.
(4) For minimum system water volume calculation, refer to Design Features & Information - Minimum System Water Volume Calculations.
(5) Nominal Free Cooling Output at 15/10°C return/supply temperatures, 3°C ambient, 20% Ethylene Glycol.
(6) Ambient temperature that Maximum Nominal DX Duty can be achieved using Free Cooling only.
(7) ESEER / SEER based upon unit operating at 12 / 7 °C return / supply temperature, 35°C ambient,

Advertising