Optic hi ll freecool, Ch illers – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 18

Advertising
background image

2 Row Free Cooling Extra Quiet


AC Fans

EC Fans

HA EC Fans

Noise Variant

No. Fans

Water Temp

ΔTs

Nomenclature

Duty (kW)

EER

ESEER

2RW

Duty (kW)

EER

ESEER

2RW

Duty (kW)

EER

ESEER

2RW

X

18

H

S

OFC075X18-66HS1

740

2.78

2.82

556

735.7

2.90

3.20

545

734

2.88

3.18

542

OFC080X18-76HS2

786

2.73

2.78

565

780.9

2.84

3.12

553

779

2.82

3.10

550

OFC084X18-77HS2

827

2.68

2.77

572

822.3

2.77

3.10

560

821

2.75

3.08

557

OFC088X18-87HS4

875

2.64

2.89

580

869.6

2.72

3.21

568

868

2.70

3.20

564

OFC091X18-87HS6

899

2.68

2.82

584

892.4

2.76

3.12

571

890

2.75

3.10

567

OFC092X18-88HS4

922

2.60

2.94

588

915.9

2.67

3.26

575

914

2.65

3.24

571

OFC095X18-88HS6

949

2.65

2.89

592

942.1

2.71

3.18

579

940

2.70

3.16

574

OFC098X18-99HS5

1008

2.46

2.88

600

999.4

2.50

3.15

586

NA

NA

NA

NA

OFC101X18-99HS6

1045

2.51

2.84

605

NA

NA

NA

NA

NA

NA

NA

NA

L

OFC075X18-66HL1

743

2.79

2.84

557

739.1

2.91

3.21

546

738

2.89

3.19

542

OFC080X18-76HL2

790

2.74

2.79

566

785.2

2.85

3.13

554

784

2.83

3.11

550

OFC085X18-77HL2

832

2.69

2.79

573

827.2

2.78

3.11

561

825

2.77

3.09

557

OFC089X18-87HL3

880

2.65

2.90

581

873.7

2.73

3.23

569

872

2.71

3.21

565

OFC091X18-87HL5

903

2.69

2.93

585

896.3

2.77

3.26

572

894

2.75

3.24

568

OFC093X18-88HL3

927

2.61

2.95

588

920.1

2.68

3.28

576

918

2.66

3.26

571

OFC095X18-88HL5

953

2.65

2.98

592

946.2

2.72

3.30

579

944

2.70

3.28

575

OFC099X18-99HL4

1014

2.46

2.90

601

1004.9

2.50

3.17

587

NA

NA

NA

NA

OFC102X18-99HL6

1048

2.52

2.93

605

NA

NA

NA

NA

NA

NA

NA

NA

(1) Duty (kW) based upon mechanical Cooling when the unit is configured with a 2 row free cooling coil.
(2) Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol.
(3) EER based upon mechanical Cooling when the unit is configured with a 2 row free cooling coil.
(4) ESEER based upon mechanical Cooling 12°C / 7°C 35°C Ambient.
(5) 2RW is the full free cooling potential at 3°C