SRD…-HART (HART positioners model code "-xHxx")

The setpoint source should be set to analog for normal operation . For maintenance functions or special requirements,

the analog setpoint can be overwritten by setting the setpoint source to digital to position the valve using a digital

communication device such as the Intelligent Field Device Configurator . The positioner will then only accept digital setpoint

commands from the configurator . After testing of the positioner, ensure that the setpoint source is set back to analog again,

otherwise the positioner will not accept any analog setpoint changes .
Valve Type
This is a single-byte field with values that defines the type of valve attached to actuator . Five types are defined:
• Globe
• Rotary
• Plug
• Butterfly
• Diaphragm
Globe
is the default .
Choose the proper valve Type .

NOTE:

N

This is for reference purposes only—the selected option does not impact the positioner’s control behavior .

Control Action
This is a one-byte flag with only two possible values . The parameter Control Action can be configured either to Direct-acting

(increasing setpoint increases pneumatic output) or Reverse-acting (increasing setpoint lowers the pneumatic output) . This

feature is also available in the push button menu of positioner’s PCB .
Control Algorithm

Valve Stem Movement

Select the Valve Stem Movement from the following options:

◊ Linear/Left Mounted (globe valve, positioner spindle to the left of the valve stem)

◊ Linear/Right Mounted (globe valve, positioner spindle to the right of the valve stem)

◊ Rotary, CCW (quarter turn, counter-clockwise to open)

◊ Rotary, CW (quarter turn, clockwise to open)

NOTE:

N

If the Type field shows a Globe valve, the Valve Stem Movement field defaults to Linear/Left Mounted .

If the Type field shows a Rotary valve, the Valve Stem Movement field defaults to Rotary, CCW .

This feature is also available in the push button menu of positioner’s PCB .

Powerup Action
This is a single-byte parameter that controls the positioner behavior with digital input when power is applied . This parameter

controls what the positioner does when the digital setpoint is lost . Online is the default .

NOTE:

N

Even though the positioner is online, it will not enable the fail safe timer until it sees the very first setpoint

communication from the host .

For Digital input, the operator may configure the Powerup mode to either Online or Fail safe . Online allows the positioner to

start responding to setpoint from control system as connection is achieved . When using Fail safe, you can define the exact

position of the control valve upon Powerup . Available options, listed under Fail Safe Config are as follows:

Configuration / Parameter