Restore Valve Specific Parameter

This function is required if a positioner is replaced without the option to

perform a new Autostart .
In this case, the function allows writing valve-specific parameters from

the replaced positioner into the new positioner . This is done by reading

the data file of one positioner mounted to a valve and writing these

values into a new positioner . This new positioner can then be adapted

to that valve without performing an Autostart .
The parameters for Lower End Position, Upper End Position, Motor

Parameter and ADC Gain have to be written into the unit . The values

of these parameters can be retrieved by means of the Parameter

List . However, if the parameters need to be edited, do so before

pressing Continue .
Due to mechanical tolerances in mounting, the adoption cannot be

optimal . Performing a new Autostart Calibration or Endpoint Calibration

is required as soon as possible .

NOTE:

N

This function is only allowed at workshop security level .

Language Download
See

“LCD” on page 59.

Change Device Type

This function lets you change the type of the device . The following

device types are available:
• SRD991
• SRD960
• SRD970
• NAF-LinkIT

THIS FUNCTION IS ONLY FOR FACTORY USAGE. THE CHANGE OF THE

DEVICE TYPE ALSO CHANGES THE BEHAVIOR OF THE DEVICE TO A

CERTAIN DEGREE.

After you change the device type, you might have to change to a different DTM to connect to the device .
Reset Device / Reboot Device
The positioner will be rebooted during this procedure . The device behaves as if the power supply will be switched off and on .

This may cause a process upset . Press Continue to reboot the positioner, or Cancel to abort .

IF YOU REBOOT THE DEVICE, IT WILL OPEN AND CLOSE THE VALVE AND DISTURB THE PROCESS.