Control Difference Time

Default for this parameter is 60 seconds . This is a 4-byte real .

7

6

5

4

3

2

1

0

Control Diff

LoLo Alarm

HiHi Alarm

Low Alarm

High Alarm

NOT USED

More Status

Failsafe

Timeout

Alarm Deadband

This 4-byte real, expressed as percentage . As an example, if the Low alarm is set to 8%, and this parameter is set to 1%, the

default, then if the Low Alarm has occurred, the positioner needs to move back to 9% in order for the alarm to be cleared from

the secondary status .
Please note, the alarm is also recorded in the historical status . Thus it is possible to check if an alarm had occurred since the

last reset of historical status .

7

6

5

4

3

2

1

0

Control Diff

LoLo Alarm

HiHi Alarm

Low Alarm

High Alarm

NOT USED

More Status

Failsafe

Timeout

Internal Electronics Temperature Lower Limit

This is a 4-byte real field that allows the user to set a minimum value for the internal electronics temperature . If the internal

temperature of the positioner is outside the Lower Temperature Limit displayed in the alarms page, an alarm will be raised .

The diagnostic bit remains set as long as the condition is valid .
Default value is – 40° C (– 40° F) . Operating the positioner below this limit may cause damage to the instrument .

7

6

5

4

3

2

1

0

NOT USED

Trim Feedback

Trim Loop

Cycle Count

Travel Sum

Config invalid

Temp low

Temp high

Internal Electronics Temperature Upper Limit

This is a 4-byte real field that allows the user to set a maximum value for the internal electronics temperature . If the internal

temperature of the positioner is outside the Upper Temperature Limit displayed in the alarms page, an alarm will be raised .

The diagnostic bit remains set as long as the condition is valid .
Default value is 80° C (176° F) . Operating the positioner above this limit may damage the instrument and violate electrical

safety conditions .

7

6

5

4

3

2

1

0

NOT USED

Trim Feedback

Trim Loop

Cycle Count

Travel Sum

Config invalid

Temp low

Temp high

Pressure Sensor Page

Air Supply Pressure Lower Limit
This is a 4-byte real, expressed in the units defined in the Units page . It specifies the lower limit of the air supply pressure . If

the air supply pressure falls below this limit a status bit will be set .
Air Supply Scaling Low
This is a 4-byte real, expressed in the units defined in the Units page . It specifies the minimum value for scaling of the air

supply pressure, which is displayed in the Device Data Screen .
Air Supply Scaling High
This is a 4-byte real, expressed in the units defined in the Units page . It specifies the maximum value for scaling of the air

supply pressure, which is displayed in the Device Data Screen .
Output Pressure Scaling High
This is a 4-byte real, expressed in the units defined in the Units page . It specifies the maximum value for scaling of the output

pressure, which is displayed in the Device Data Screen .

Additional Status

Page 89

August 2014