Data screen – Badger Meter SRD/SRI Valve Positioners User Manual

Page 95

Advertising
background image

Data Screen

For Profibus devices, an additional Data Screen may be opened to display additional Profibus specific parameters . To view

the Profibus Data, select View – Profibus Data . This function opens a modeless dialog . The displayed information updates

approximately once every two seconds .

Fields

Description

Readback The actual position of the actuator/valve within the travel span in units of PV-SCALE .

Position D The current position of the actuator/valve (discrete) . Possible values are: NOT INITIALIZED (before an autostart

has been performed), CLOSED, OPENED and INTERMEDIATE .

FB-Mode

Actual Mode of the Function Block .

SP

Setpoint SP in units of PV-SCALE . This setpoint is used as desired value , when the function block is in Mode

AUTO and the status of SP is ok (for example, Good (Non Cascade) = 0x80) .

RCAS_IN

Setpoint RCAS_IN in units of PV-SCALE . This setpoint is normally transmitted by a DCS System . This setpoint is

used as desired value , when the function block is in Mode RCAS and the status of RCAS_IN is ok (for example,

Good (Cascade) =0xC0) .

RCAS_

OUT

Setpoint RCAS_OUT in units of PV-SCALE with status, which is used as input for the function block algorithm .

Depending on the mode of the function block contains the setpoint SP or RCAS_IN . RCAS_OUT is offered for

the DCS- System or other function blocks .

OUT

Output Setpoint of the function block in units of OUT-SCALE with status . It is valid, when the function block is

in mode AUTO or RCAS . In mode MAN, this value can be specified by the operator/engineer .

Profibus Function Block Page

For the detailed configuration of the Profibus Function Block parameters, use the Profibus Function Block page .

Fields

Entries

Target Mode

Contains the desired mode of the function block .

PV-SCALE:

Conversion of a process value in the defined engineering units to a normalized value in percent as the

input value of the function block . It contains the high and low scale values, engineering units code,

and number of digits to the right of the decimal point . As default, PV-PSCALE is configured to percent,

meaning that the Variables SP, Readback, RCAS_IN and RCAS_OUT, which are depending on PV-SCALE, are

displayed in the range 0…100% .

OUT-SCALE:

Conversion of the normalized Output Signal (in percent) of the function block to the OUT parameter in the

defined engineering units . It contains the high and low scale values, engineering units code, and number

of digits to the right of the decimal point . As default, OUT- SCALE is configured to percent, meaning that

the Variable OUT is displayed in the range 0…100% .

Simulation

Allows definition of a value and a status . When Simulation is enabled, this value and status is given in

Readback instead of the real position of the actuator/valve . This set of parameters is intended only for

commissioning and maintenance reasons .

Profibus Configurations

Page 95

August 2014

POS-UM-00011-EN-02