Profibus configurations, Comm-dtm – Badger Meter SRD/SRI Valve Positioners User Manual
Page 93
![background image](/manuals/371280/93/background.png)
PROFIBUS CONFIGURATIONS
Comm-DTM
We recommend using the communication DTM for Profibus distributed by Softing . This driver is not included in the
modeminstall.exe or the srdinstall.exe .
The driver can be downloaded and updated from: http://www .softing .com, but requires a USB-dongle that has to be
purchased from Softing directly . In addition, an interface (PROFIcard by Softing) to connect the PC or workstation to a
Profibus DP segment coupler is required .
Use the following DPV1 parameters for
setting up the Comm-DTM .
Settings:
The settings can be found under
Parameter for the Comm-DTM
(<0, PROFIdtm>PROFIdtm DPV1) .
Miscellaneous
Baud Rate: 93 .75 kBits/s
Highest Station Address: 126
Max . retry Limit: 1
Gap Update Factor: 10
Timing
Slot Time: 4000
Quiet Time: 0
Target Rotation Time: 85000
Setup Time: 250
Min . Station delay: 450
Max . Station delay: 1000
Profibus Configurations
Page 93
August 2014
POS-UM-00011-EN-02